Checkout, Caution, A. b. c – Honeywell CHRONOTHERM T8624C User Manual

Page 11

Advertising
background image

11

68-0134

T8624C,D

INSTALLATION • CHECKOUT

Fig. 11—Mounting thermostat on subbase.

M3764

PM

RETURN

MON

HEAT ON

SYSTEM

AUTO

PM

RETURN

MON

HEAT ON

SYSTEM

RUN

PROGRAM

TIME

TEMPERATURE

PRESENT

SETTING

SKIP

NEXT

PERIOD

CHANGE
TO LAST

PERIOD

SET

PRESENT
DAY/TIME

HOLD
TEMP

AHEAD

WARMER

BACK

COOLER

A.

B.

C.

HEAT

AUTO

COOL

OFF

ON AUT

O

FAN

PERIOD

WAKE

SLEEP

RETURN

LEAVE

DAY

SET

HEAT/COOL

Checkout

HEATING

Move the system switch to HEAT and the fan switch

to AUTO. Press WARMER key until the setting is about
10

°

F [6

°

C] above room temperature. Heating should

start (both stages if multistage), and the fan should run
(may be a short delay on forced air systems). Press
COOLER key until the setting is about 10

°

F [6

°

C]

below room temperature. The heating equipment should
shut off, followed by the fan.

NOTE: On an AUTO changeover thermostat, the cool-

ing temperature must be set at least 3

°

F [2

°

C] above

the heating temperature, or display will flash.

COOLING

CAUTION

Do not operate cooling if outdoor temperature
is below 50

°

F [10

°

C]. Refer to manufacturer

recommendations.

NOTE: When cooling setting is changed, thermostat

will wait up to five minutes before turning on the
cooling equipment. This delay is to protect the com-
pressor.

Move the system switch to COOL and the fan switch

to AUTO. Press COOLER key until the setting is about
10

°

F [6

°

C] below room temperature. The cooling

equipment and fan should start (both stages if multi-
stage). Press WARMER key until the setting is about
10

°

F [6

°

C] above room temperature. The cooling

equipment and fan equipment should stop.

NOTE: On an AUTO changeover thermostat, the heat-

ing temperature must be set at least 3

°

F [2

°

C] below

the cooling temperature, or display will flash.

FAN

Move the system switch to OFF, and the fan switch to

ON. The fan should run continuously. When the fan
switch is in the AUTO position, the fan operates directly
with the thermostat call for cooling and also with the

!

Advertising