Foster RBC20-60 User Manual

Page 12

Advertising
background image

11

P86 Alarm

Buzzer Function

NO

YES

NO

P87 Air

Probe

Offset °K

-15

15 0

P88

Coil Probe Offset

°K

-15

15

0

P89 Food

1

Offset

°K

-15

15 0

P90

Food 2 Enable

Function

NO

YES

NO

P91 Food

2

Offset

°K

-15

15 0

P92

Food 3 Enable

Function

NO

YES

NO

P93 Food

3

Offset

°K

-15

15 0

P94 Address

Integer

1

255

255

Parameter Definitions
Pre-Chill
P01

Pre-Chill Enable
The air temperature, which the air probe must read before the condensing system is de-energised in the chill
mode of the Pre-Chill Program.
Range -15°C to 15°C.

P02 Chill

Time

The period Pre-Chill is in the chill mode prior entering the Hold Mode.

Range 5 minutes to 60 minutes.


P03 Hold

Temp

The temperature, which the air probe must read before the condensing system is de-energised in the Hold mode

of the Pre-Chill program.

Range -15°C to 15°C.

Soft-Chill
P04 Air

Temp

The temperature, which the air probe must read before the condensing system is de-energised in the chill mode
of the Soft-Chill Program.
Range -10°C to 15°C.

P05 Chill

Time

The period Soft Chill program is in chill mode prior to entering Hold mode in a time based chill cycle.

Range 5 minutes to 480 minutes.


P06 Chill

Temp

The temperature, which the Food Probe 1 must read before the condensing system is de-energised in the chill
mode of the Soft Chill program prior to entering the Hold mode of a temperature based cycle.
Range -5°C to 15°C.

P07 Hold

Temp

The temperature, which the air probe must read before the condensing system is de-energised in the Hold mode
of the Soft Chill program.

Range -5°C to 15°C.

Hard Chill
P08 Air

Temp

The temperature, which the air probe must read before the condensing system is de-energised in the chill mode
of the Hard Chill Program.
Range -20°C to 15°C.

P09 Chill

Time

The period Hard Chill program is in chill mode prior to entering Hold mode in a time based chill cycle.
Range 5 minutes to 480 minutes.

P10 Chill

Temp

The temperature, which the Food Probe 1 must read before the condensing system is de-energised in the chill
mode of the Hard Chill program prior to entering the Hold mode of a temperature based cycle.
Range -15°C to 15°C.

P11 Hold

Temp

The temperature, which the air probe must read before the condensing system is de-energised in the Hold mode
of the Hard Chill program.

Range -15°C to 15°C.

P12 Change

Time

The percentage period of a time based chill cycle, which is to have passed before automatically adjusting the air
temperature set point to 1°C.The range is adjustable in 5% increments.

Range 05% to 95%.