P27

Chill Temp Minimum

The minimum value that the temperature, which Food Probe 1 must read before the condensing system is de-
energised in the chill mode of the Professional 1 program, prior to entering the Hold mode of a temperature based
cycle, which it can be adjusted to by the operator.

Range -20°C to -5°C.

P28

Chill Temp Maximum

The maximum value that the temperature, which Food Probe 1 must read before the condensing system is de-
energised in the chill mode of the Professional 1 program, prior to entering the Hold mode of a temperature based
cycle, which it can be adjusted to by the operator.

Range -5°C to -15°C.

P29

Hold Temp Std
The standard temperature, which the air probe must read before the condensing system is de-energised in the
Hold mode of the Professional 1 Program.
Range -15°C to 15°C.

P30 Hold

Temp

Minimum

The minimum value that the Hold temperature set point can be adjusted to by the operator in the Professional 1
program.
Range -10°C to 0°C.

P31 Hold

Temp

Maximum

The maximum value that the Hold temperature set point can be adjusted to by the operator in the Professional 1
program.
Range 0°C to 10°C.

P32 Change

Time

The percentage period of a time based chill cycle, which is to have passed before automatically adjusting the air
temperature set point to 1°C.The range is adjustable in 5% increments.

Range 05% to 95%.

P3

The percentage of a temperature based chill cycle, which is passed before automatically adjusting the air
temperature set point to 1°C.The range is adjustable in 5% increments.

3 Change

Temp

Range 5% to 95%.

Pr
P3

The standard temperature, which the air probe must read before the condensing system is de-energised in the
chill mode of the Professional 2 Program.

ofessional 2

4

Air Temp Std

Range -20°C to 15°C.

P35

Chill Time Std
The standard period Professional 2 program is in chill mode prior to entering Hold mode in a time based chill
cycle.
Range 5 minutes to 480 minutes.

P36

Chill Time Minimum

The minimum period Professional 2 program is in chill mode prior to entering Hold mode in a time based chill
cycle that it can be adjusted to by the operator.

Range 5 minute to 60 minutes.

P37

Chill Time Maximum

The maximum period Professional 2 program is in chill mode prior to entering Hold mode in a time based chill
cycle that it can be adjusted to by the operator.

Range 60 minute to 480 minutes.

P38

Chill Temp Std
The standard temperature, which the Food Probe 1 must read before the condensing system is de-energised in
the chill mode of the Professional 2 program prior to entering the Hold mode of a temperature based cycle.
Range -15°C to 15°C.

P39

Chill Temp Minimum

The minimum value that the temperature, which Food Probe 1 must read before the condensing system is de-
energised in the chill mode of the Professional 2 program, prior to entering the Hold mode of a temperature based
cycle, which it can be adjusted to by the operator.

Range -20°C to -5°C.