P83 high alarm delay, P84 alarm time – Foster RBC20-60 User Manual

Page 18

Advertising
background image

17

NO = No safety door switch fitted. YES = Safety door switch fitted.

Note: Usually fitted to the evaporator fan door on Modular Blast Chillers.


P79

Door Switch 1

Determines if a door switch is fitted or not, and consequently dictates Evaporator Fan operation, UV Sanitisation
operation and door alarm activation’s. Also used to initiate the controller from the energy saving mode.

NO = No door switch fitted. YES = Door switch fitted.

P80

Door Stop

The delay period between the door being opened and the condensing unit stopping (only active if the ‘Door
Switch’ is set to ‘YES’).

00 minutes = Condensing unit stops instantaneously. 01 to 30 minutes = Delay before unit stops.

P81 Door

Alarm

Delay

The delay following the ‘Door Stop’ period before the door open alarm sounds. Therefore if the ‘Door Stop’ is set
for 1 minute, and the ‘Door Alarm’ is set to 5 minutes, the door alarm will sound 6 minutes after the door was
opened. (Only active if ‘Door Switch’ = YES).

00 minutes = //instantaneous door alarm. 01 to 30 minutes = Delay before alarm sounds.

P82 High

Alarm

Temp

The temperature at which the alarm will sound to warn that the measured air temperature value is too high. The
alarm sounding is dependent upon the selected program and the stage of the cycle. I.e. during a chill cycle if the
measured temperature is greater than or equal to program air set point temperature + chill hysteresis + high
alarm temperature value (after the appropriate alarm delay period) the alarm will sound. Similarly if the measured
hold temperature is greater than or equal to program hold set point + hold hysteresis + high alarm temperature
value the alarm will sound.

Range 1°C to 50°C.

P83 High

Alarm

Delay

The delay period between a temperature alarm condition occurring.

00 minutes = Instantaneous audible alarm. 01 to 120 minutes = period of delay.

P84 Alarm

Time

The length of time, which the alarm will sound for an end of program cycle alarm or any other alarm warning prior
to automatically muting.
00 minutes No alarm. 01 to 120 minutes = Alarm energised period.

P85

Alarm Repeat Interval

The length of time between an acknowledged alarm being automatically muted and the alarm sounder being re-
energised.

00 minutes = No alarm reminder. 01 to 480 minutes = Alarm reminder period.

P86 Alarm

Buzzer

Enables or disables the board alarm buzzer.

NO = Alarm disabled. YES = Alarm enabled.

P87

Air Probe Offset

Allows the value of the Air Probes to be offset allowing the product temperature to be accurately measured.

Range -15°C to +15°C

P88

Coil Probe Offset

Allows the value of the Evaporator Coil Probe to be offset allowing the coil temperature to be accurately
measured.

Range -15°C to +15°C.

P89

Food 1 Offset

Allows the value of Food Probe 1 to be offset allowing for the product temperature to be accurately measured.

Range -15°C to +15°C.

P90

Food 2 Enable

Determines whether a second Food Probe is fitted.

NO = No second food probe fitted. YES = Second food probe fitted.

P91

Food 2 Offset

Allows the value of Food Probe 2 to be offset allowing for the product temperature to be accurately measured.

Range -15°C to +15°C.

P92

Food 3 Enable

Determines whether a third Food Probe is fitted.