Trigger output, Master alarm – Fluke NetDAQ 2645A User Manual

Page 46

Advertising
background image

2640A/2645A NetDAQ

Users Manual

2-14

+

9-16V

DC PWR

MA TO TI

ALARM/TRIGGER I/O

TR

3

2

1

0

+

+

MA
TO
TI

DC Positive Input
DC Negative Input
Master Alarm Output
Trigger Out Output
Trigger In Input
Signal Ground

Instrument

Connector

+

2
3
TR

Instrument

Function

Connector

Figure 2-6. ALARM/TRIGGER I/O Connector

Trigger Output

2-17.

Trigger Output uses terminals TO and GND, and is a TTL signal that goes to a
logic low for 125 µs every time a scan begins. Use the Trigger Output to trigger
other instruments via their Trigger Input connection and to interface with external
equipment. To enable or disable the Trigger Output, see "Trigger Out" in Chapter
3 of this manual. The trigger output default is OFF. See Table A-5 in Appendix A
for complete specifications.

Master Alarm

2-18.

Master Alarm uses terminals MA and GND. It is a TTL signal that goes to a logic
low when any channel is in alarm while the instrument is scanning. This TTL
signal output can interface with external equipment such as warning lights,alarms,
paging systems, etc. See Table A-6 in Appendix A for complete specifications.