Installation – FMI VF48H(I)(R)A User Manual

Page 10

Advertising
background image

www.fmiproducts.com

124386-01A

10

10 FOOT RULE

All flue gas outlet chimney terminations must

extend a minimum of 3 feet in height above

highest point where it passes through the roof

and must be at least 2 feet above highest point

of the roof that is within a horizontal distance

of 10 feet (see Figure 17).

INSTALLATION

Continued

FINISHING FIREPLACE

Combustible materials, such as wallboard,

gypsum board, sheet rock, drywall, plywood,

etc. may make direct contact with sides and

top around the fireplace face. It is important

that combustible materials do not overlap face

itself. Brick, glass, tile or other noncombustible

materials may overlap front face provided they

do not obstruct essential openings like louvered

slots or any other opening. When overlapping

with a noncombustible facing material, use only

noncombustible mortar or adhesive.

24" Min.

24" Min.

18"

Min.

Typ.

Figure 16 - Multiple Chase Installation

10'

2' Min.

10'

3' Min.

2' Min.

3' Min.

Level of

Flue Gas

Outlet

Figure 17 - 10 Foot Rule

CAUTION: All gas piping

and connections must be tested

for leaks after the installation

is completed. After ensuring

that the gas valve is on, apply

soap and water solution to all

connections and joints. Bubbles

forming show a leak. Correct

all leaks at once. DO NOT USE

AN OPEN FLAME FOR LEAK

TESTING AND DO NOT OPER-

ATE ANY APPLIANCE IF A LEAK

IS DETECTED. LEAK TESTING

SHOULD BE DONE BY A QUALI-

FIED SERVICE PERSON.

WARNING: Do not operate an

unvented gas log set in this fire-

place with the chimney removed.

If you install a decorative gas appliance

(vented gas log), the decorative gas appliance

must comply with the Standard for Decorative

Gas Appliance for Installation in Solid Fuel

Burning Fireplaces, ANS Z21.60 or Z21.84

and shall also be installed in accordance with

the National Fuel Gas Code, ANSI Z223.1/

NFPA 54 latest edition.

WARNING: If fireplace has

been used for wood burning,

firebox and chimney must be

cleaned of soot, creosote and

ashes by a qualified chimney

cleaner. Creosote will ignite if

heavily heated.

WARNING: When using

a decorative vented gas log,

damper must be removed or

permanently locked in the fully

open position and glass doors

must be in fully open position.