INSTALLATION

Continued

Figure 9 - Elbow Offset

B

A

Screws

FIRESTOP SPACERS (FS-10)

Firestop spacers are required at each point

where chimney penetrates a floor space.

Their purpose is to establish and maintain

required clearance between chimney and

combustible materials. When pipe passes

through a framed opening into a living space

above, firestop must be placed onto ceiling

from below as shown in Figure 10.
They also provide complete separation from

one floor space to another or attic space as

required by most codes. When the double wall

pipe passes through a framed opening into an

attic space, the firestop must be placed into

an attic floor as shown in Figure 11.

Figure 10 - Firestop Spacer with Living

Space Above Ceiling

Figure 11 - Firestop Spacer with Attic

Space Above Ceiling

Existing

Ceiling

Frame

Firestop

Spacer

Screws or

Staples

(Min. of 8)

Firestop

Spacer

Screws or Staples

(Min. of 8)

PENETRATING ROOF

To maintain a 2" clearance to pipe on roof with

a pitch, a rectangular opening must be cut.
1. Determine center point through which pipe

will penetrate roof.

2. Determine center point of roof. Pitch is

the distance the roof drops over a given

span, usually 12".

3. Use roof opening chart (Figure 12) to

determine correct opening length and

flashing required.

4. Remove shingles around opening mea-

sured. Cut out this section.

5. Add next sections of pipe until end

penetrates roof line. Check to see that

proper clearances are maintained. Extend

chimney by adding sections of double wall

pipe until pipe is minimum of 30" above

highest point of roof cutout. Termination

and chimney must extend a minimum of

36" above highest point where it passes

through roof.

Pitch

Slope

Opening

"A" Max.

Used Flashing

Model No.

Flat

19.5"

V6F-10DM

0-6/12

26.6°

22'

V6F-10DM

6/12-12/12 45.0°

27"

V12F-10DM

Existing

Ceiling

Frame

19.5" Min.

30" Min.

2" Min.

2" Min.

2" Min.

Opening "A"

Figure 12 - Roof Opening Measurements