Sup series™ ups 700va & 1kva – Falcon SUP1.0K-1C User Manual

Page 18

Advertising
background image

SUP Series™ UPS

700VA & 1kVA

Model Number

SUP700-1C

SUP1.0K-1C

Nominal VA

700

1000


Electrical Input
Nominal AC Voltage

120V or 230V

120V or 230V

Current-Amps

7 (120V), 3.6 (230V)

10 (120V), 5.2 ( 230V)

AC Voltage Window

-21% to 25%

Frequency

50/60 Hz (Auto – Tracking)

Frequency Range

47 – 63Hz

UPS is designed for use on 120V domestic or 230V international utility power with neutral, line and ground connections.


Electrical Output
Watts

490

650

Nominal AC Voltage

120V

120V

Frequency

50/60 Hz (Auto-Tracking)

On-Line Voltage Regulation

± 8%

On Battery Voltage Regulation

± 8% Typical (prior to low battery warning)

Waveform

True Sinewave

Surge Protection

125 Joules MOV

Unit Protection

Short Circuit, Overload & Over Temperature

Efficiency AC to AC (Typical)

97% (120Vac Input), 90% (230Vac Input)


Battery
DC Voltage

24V

24V

Type

12V, 7AH x 2

Lead Acid Maintenance-Free

12V, 9AH x 2

Lead Acid Maintenance-Free

Back Up Time @ Full Load
@ 1/2 Load

5 Minutes

12 Minutes

4.5 Minutes

11 Minutes

Recharge Time

5 Hours to 90%

Battery times are approximate.


Transfer Time
Bypass to Inverter

Black-out, 3ms / Brown-out, 0ms

Inverter to Bypass

0ms


Electrical Connections
Input

1 - 6’ Cord with 5-15P &

1 – 6’ Cord with Schuko

1 - 6’ Cord with 5 -15P &

1 – 6’ Cord with Schuko

Output

(3) 5-15R

(3) 5-15R


Environmental
Operating Temperature

0º C - 40º C (32º F to 104º F)

Altitude

7,000 Feet

Humidity

10% to 95% Non – Condensing

Cooling

Low Velocity Forced Air Fans

Audible Noise @ 1 meter

< 45dBA


Controls and Indicators
Control

One Main Control Button – UPS On/Off, Self Test, Reset & Silence Alarms

Selection Control

Two LCD Metering Scroll Function Select Buttons

LCD Display

AC Input Voltage, AC Output Voltage, Output Frequenc y, DC Battery Voltage, Internal UPS

Temperature,

Timer – Minutes to Shutdown, Hours to Restart, Battery – Remaining Battery Time

LCD Operational Symbols

Overload, Load Level, UPS is Loaded, Normal Mode, Buck Mode, Boost Mode, Timer Enabled,

High Temperat ure, Fan Off, Alarm Off, UPS Fault, Battery Low, Battery Level

Audible Alarms

Low Battery, Defective Battery, Low Battery, Overload, Over Temperature, AC Out of Range

Communications

RS-232 Serial Port and Contact Closure Signal interface (Bundled UPSil on 2000 Software)


Mechanical
Dimensions H x W x D
Inches (mm)

7.9 x 7.1 x 14.2 (200 x 180 x 360)

Weight lb. (kg)

33.1 (15)

33.1 (15)

Agency Listing

UL1778, CUL, FCC Class A

Note: The UPS will go to Green Mode whenever the output load is under 30 watts.

Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720

www.falconups.com - email:[email protected]

©2004 Falcon

®

Electric, Inc. All rights reserved. Falcon

®

and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc.

All other brand names and trademarks are the property of their respective owners.
The information and specifications stated in this document are subject to change without notice. 01-07-04 MD44034-A

17

Advertising
This manual is related to the following products: