Venting installation – FMI WCM-42G User Manual

Page 12

Advertising
background image

www.fmiproducts.com

122271-01D

12

VenTing inSTallaTion

Continued

10 FOOT RULE

All flue gas outlet chimney terminations must

extend a minimum of 3 feet in height above the

highest point where it passes through the roof

and must be at least 2 feet above the high-

est point of the roof that is within a horizontal

distance of 10 feet (see Figure 20).

FINISHING FIREPLACE

Combustible materials, such as wallboard,

gypsum board, sheet rock, drywall, plywood,

etc. may make direct contact with sides and top

around the fireplace face. It is important that

combustible materials do not overlap the face

itself. Brick, glass, tile or other noncombustible

materials may overlap the front face provided

they do not obstruct essential openings like

louvered slots or any other opening. When

overlapping with a noncombustible facing

material, use only noncombustible mortar or

adhesive.

24" Min.

24" Min.

18"

Min.

Typ.

Figure 19 - Multiple Chase Installation

10'

2' Min.

10'

3' Min.

2' Min.

3' Min.

Level of

Flue Gas

Outlet

Figure 20 - 10 Foot Rule

Terminations/Spark Arrestor

The fireplace system must be terminated with

the listed round top or chase terminations. In

any case, refer to the installation instructions

supplied with the termination.

CAUTION: Do not seal open-

ings on the rooftop flashing. Fol-

low the installation instructions

provided with the termination

being used.

Secure

Termination

to Outer

Pipe with 3

Screws

RTL-10D

Level of

Flue Gas

Outlet

Stainless

Inner Flue

Pipe

Waterproof

Caulking

Storm

Collar

Flashing

Underlap

Shingles

Figure 18 - Termination

Overlap

Shingles (Top

and Sides of

Flashing Base)

CHASE INSTALLATIONS

Instructions for chase installations are

included with the chase style termination

chosen. In a multiple chase installation, be

sure to provide adequate distance between

terminations to prevent smoke spillage from

one termination to another. We suggest that

terminations be separated at least 24", center

to center and stacked at a vertical height dif-

ference of 18" (see Figure 19).
Note: If a decorative shroud is to be installed,

contact the manufacturer for specifications.