TROUBLEShOOTING

MILLIVOLT SYSTEM

Note: Before troubleshooting the system, make sure the gas shutoff valve is ON.
The two most common causes of a malfunctioning gas appliance are:
1. Loose wiring connections
2. Construction debris clogging the pilot and/or gas control valve filter

OBSERVED PROBLEM

Pilot will not light

Pilot will not stay lit

No gas to burner, although wall

switch and valve are set to the

ON position

Frequent pilot outage

Pilot goes out when wall switch

is ON

POSSIBLE CAUSE

1. No gas supply or shutoff

valve is OFF

2. Air in gas line

3. Construction debris clog-

ging pilot orifice

4. Low gas pressure

5. Control valve knob is not on

the PILOT position

6. Kinked pilot line

7. Bad valve

1. Loose wiring on thermopile

to control valve.

2. No millivolt current is being

sent back to regulator

3. If valve knob and wall switch

are in the ON position, prob-

able defective control valve

1. Wall switch wires defective

2. Thermopile or sensor not

generating sufficient voltage

1. Pilot flame may be too

low, causing safety pilot to

“drop out”

1. Millivolt output on thermo-

pile too high

REMEDY

1. Check to see if you have gas

supply

2. Hold regulator control valve

in the PILOT position for 2 to

3 minutes to purge air. If you

smell gas stop and wait for a

few minutes before trying to

light the fireplace

3. Remove debris and dirt, in-

spect and clean any other

possible obstructions

4. Contact your gas supplier

5. Refer to section on pilot

lighting

6. Have a qualified technician

replace pilot line

7. Replace control valve (see

Replacement Parts and Acces-

sories, page 19)

1. Check wiring connections.

Refer to wiring diagrams on

page 15

2. Have a qualified technician

check millivolts

3. Have a qualified technician

replace valve (see Replace-

ment Parts and Accessories,

page 19)

1. Check electrical connections

and wires for continuity

2. See Pilot will not stay lit,

above

1. Clean and adjust pilot flame

for maximum flame impinge-

ment on thermopile

1. Have a qualified technician

replace thermopile