4.4.4.

Reading TIWAY data map descriptor examples

4.4.4.1.

Reading data from contiguous PLC data memory locations

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length,
C01_RAW16_PLC01, RAW16_Data,

0, RDBC,

PLC_01,

IE_Ladder,

0,

10,


Scan_Interval
0s

The above map descriptor will continuously read 10 data elements starting from address 0 of type “IE_Ladder” from
PLC_01. The data will be stored in the data array called “RAW16_Data” from an offset of 0.

4.4.4.2.

Reading data from random PLC data memory locations

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, TIWAY_Address_List, Length,
C02_RAW16_PLC01, RAW16_Data,

10,

RDBC, PLC_01, Variable,

5

9,

2,


Scan_Interval
0s

The above map descriptor will continuously read 2 data elements from address 5 and 9 of type “Variable” from
PLC_01. The data will be stored in the data array called “RAW16_Data” from an offset of 10. The data will be
stored at offsets 10 and 11.





4.4.4.3.

Reading Drum_Count_Preset data from contiguous PLC data memory locations

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length,
C08_RAW16_PLC01, RAW16_Data,

70,

RDBC, PLC_01, Drum_Count_Preset,

0,

5,