5. Configuring the FieldServer as a TIWAY Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer

instruction Configuration mM

anual

(Virtual PLC)

. The information that follows describes how

to expand upon the factory defaults provided in the configuration files included with the
FieldServer (See “.csv” files on the driver diskette).

This section documents and describes the parameters necessary for configuring the
FieldServer to communicate with a TIWAY Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data
required. In order to enable the FieldServer for TIWAY communications, the driver
independent FieldServer buffers need to be declared in the “Data Arrays” section, the
FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the
data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors”
section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.

5.1. Server Side Connection Descriptors

Section Title

Connections

Column Title

Function

Legal Values

Port

Specify which port the device is
connected to the FieldServer

P1-P8

Protocol

Specify protocol used

TIWAY, TIWAY_BDLC

Baud*

Specify baud rate

110 – 115200, standard
baud rates only

Parity* Specify

parity

Even, Odd, None, Mark,
Space

Data_Bits*

Specify data bits

7, 8

Stop_Bits*

Specify stop bits

1

Handshaking*

Specify hardware handshaking

RTS, RTS/CTS, None

Server_Hold_Timeout*

Specifies time FieldServer will
reserve server side connection
while waiting for the Client side
to update data in Data_Array (if
necessary)

>1.0s