The above map descriptor will continuously write data of type “Loop_Gain” to 2 PLC data memory addresses of 5
and 9. The data to write will be collected from the data array “FLOAT_Data” from offsets 0 and 1.


4.4.5.3.

Writing the same value to a block of contiguous PLC data memory locations

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length,
C18_FLOAT_PLC254, FLOAT_Data,

10,

WRBC, PLC_254, Loop_Reset,

0,

3,


TIWAY_Fill_Block_Value, Scan_Interval
50.5, 0s


The above map descriptor will continuously write a value of 50.5 of type “Loop_Reset” to 3 contiguous PLC data
memory addresses starting from 0.

4.4.5.4.

Writing Drum_Count_Preset data to contiguous PLC data memory locations

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length,
C08_RAW16_PLC01, RAW16_Data,

70,

WRBC, PLC_01, Drum_Count_Preset,

0,

5,


Preset_Step_List, Scan_Interval
5 8 9 33 49,

0s


The above map descriptor will continuously write data of type “Drum_Count_Preset” to 5 PLC data memory
addresses. The data to write will be collected from the data array “RAW16_Data” from an offset of 70. The Preset
Steps associated with the addresses are (address 0):5, (address 1):8, (address 2):9, (address 3):33, and (address
4):49.

4.4.5.5.

Writing Drum_Count_Preset data to random PLC data memory locations

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, TIWAY_Address_List,
C08_RAW16_PLC01, RAW16_Data,

70,

WRBC, PLC_01, Drum_Count_Preset,

5

9,


Length, Preset_Step_List, Scan_Interval