5.3.3.

Serving TIWAY data map descriptor example

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length
S01_RAW16_PLC0, RAW16_Data, 0,

Server, PLC_01, IE_Ladder,

0,

10

The above map descriptor serves 10 data elements starting from address 0 of type “IE_Ladder” for PLC_01.

5.3.4. Serving

Drum_Count_Preset

TIWAY data map descriptor example

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length,
S10_RAW16_PLC01, RAW16_Data,

71,

Server, PLC_01, Drum_Count_Preset,

0,

4,


Preset_Step_List
3 5 9 167

The above map descriptor serves 4 data elements starting from address 0 of type “Drum_Count_Preset” for
PLC_01. Each address location is contiguously associated with a preset step value from the Preset_Step_List field.

5.3.5.

Serving PLC status data map descriptor example

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Length
S36_PRIM_STATUS, Status,

0,

Server, PLC_01, Status_Primitive, 3

The above map descriptor serves 3 status data elements for PLC_01 in the data array “Status” starting from offset
0.