Portable Dryer Troubleshooting

39

The B. GND terminal is used to ground the burner and to complete the flame current signal circuit. This terminal is

new for systems that used the older version of the Fenwal board. This terminal must be connected to the burner
(chassis) ground not only to ensure the best, long term, stable flame signal, but also to ground the burner for
proper sparking.

The use of a burner ground terminal eliminates the problem of loss of flame sense signal due to a missing or loose

neutral or ground (green) wire at the 120 VAC power source. The new board has been designed such that reversing
the polarity of the 120 VAC line does not cause a loss of flame signal. Thus providing a more reliable flame signal
along with a reduction of nuisance lockouts, due to its design and the use of the B. GND terminal.

New Fenwal Board Wiring

L2
V2

(B) V1

S1

E2

GAS

VALVE

H.V.

E1

120

VAC

BURNER

NEU.

HOT

L2

GAS

VALVE

120

VAC

NEU.

HOT

V2

L1

V1

NC

BURNER

H.V.

S1

B. GND

IGNITOR

Part No. HF-4624

Flame Safety Board

BURNER
GROUND
(B. GND)

Old version with Remote Flame Sense.

New version with Remote Sense using existing

spark and remote sense electrodes.

FLAME ROD

Note that terminal E2 on the old version has been replaced by terminal B.GND on the new board.

(A) L1

Wiring Reference