Operation - electrical, Direct gas burner sequence, Electrical sequence – Greenheck Fan Make-Up Air Unit VSU User Manual

Page 13: Supply fan contact closed, Heat contact closed, Flame safeguard (fsg) sequence, Supply fan contact (s2) closed, Heat contact (s4) closed

Advertising
background image

13

Model VSU Make-Up Air

®

®

®

®

®

Direct Gas Burner Sequence

1. Supply Fan Contact Closed

• Power passes to the supply fan and heat switch

2. Heat Contact Closed

• Power passes to the heat relay then to the

Flame Safeguard

3. Flame Safeguard (FSG) Sequence

• Checks for proper airflow
• Verifies no flame present at burner
• Initiates 10 second prepurge
• Sends power to open pilot gas valve (V1) and

energizes the spark generator (SG) (clicking of
the spark generator may be heard)

• Tries for up to 10 seconds to light pilot and

confirm flame

• Powers the main gas valves open
• Shuts down spark generator
• Continuously monitors the flame and airflow
• Performs self-diagnostic check every five

seconds

Operation - Electrical

Electrical Sequence

1. Supply Fan Contact (S2) Closed

• Power passes to damper which opens
• When damper is fully opened, damper relay

(D1) is energized an optional N.O. damper limit
switch (DL1) closes

• Power passes through a N.C. fault contact on

soft starter (PST(FAULT))

• Power passes to and energizes supply fan relay

(RI)

• Supply fan starts

2. Heat Contact (S4) Closed

• Power passes to N.O. fan relay which is

energized and closed

• Power passes to inlet air sensor contact (TS)

which is energized and closed if the inlet air
temperature is below the set point

• Power passes to and energizes the heat relay

(RH)

• N.O. heat relay contact (RH) closes
• Power passes to and energizes terminal 5 of the

Flame Safeguard (FSG).

• Power passes to N.C. high limit control contact

(HLC) which is closed if temperature has
remained below the high limit set point

• Power passes to terminal 6 of the Flame

Safeguard (FSG)

• Flame Safeguard (FSG) begins direct gas burner

sequence (see Direct Gas Burner sequence)