Troubleshooting, Heater does not operate – Greenheck Fan Make-Up Air Unit VSU User Manual

Page 15

Advertising
background image

15

Model VSU Make-Up Air

®

®

®

®

®

Heater Does Not Operate

Does not attempt to light (No visible spark)

Troubleshooting

24 VAC between

terminals W1 and X?

Heat Switch (S4) Off

(Turn Heat Switch (S4) On)

Heat Switch Not Wired

(Wire Heat Switch (S4))

115 VAC between

terminals 102 and 101?

Primary Fuses Blown

(Replace Fuses)

Main Transformer (TR4) Defective

(Replace Transformer)

115 VAC between

terminals 104 and 101?

High Limit (HLC) Tripped

(Reset/Replace High Limit (HLC))

(Check on cause of control loss)

Continuity between

terminals 107 and 108?

115 VAC between

terminals 103 and 101?

Inlet Air Sensor (TS) Holding

(Adjust TS setting — Reference Blower Start-Up Step #6)

Heat Relay (RH) Defective

(Replace Heat Relay (RH))

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Airflow Switch (PS) Holding for Proper Airflow

(Correct airflow across burner)

(Reference Direct Gas Start-Up Step #3)

The power light on the flame safeguard should

blink approximately every 5 seconds as it

performs a self-diagnostics check.

At this time the heater should attempt to light.

(The pilot light on the flame safeguard should illuminate).