Model VSU Make-Up Air

®

®

®

®

®

6. Set-up Optional Components

Adjust the settings on the optional components. See
the Control Center Layout in the Reference section for
location of optional components.

• Heating Inlet Air Sensor

Typical setting: 60-70ºF

NOTE

The most accurate way to measure the air volume is

by using a pitot traverse method downstream of the

blower. Other methods can be used, but should be

proven and accurate.

IMPORTANT

Changing the air volume can significantly increase

the motor’s amps. If the air volume is changed,

the motor’s amps must be checked to prevent

overloading the motor.

NOTE

To ensure accuracy, the dampers are to be open

when measuring the air volume.

5. Air Volume Measurement & Check

Measure the unit’s air volume (cfm) and compare it with
it’s rated air volume. If the measured air volume is off,
adjust the fan’s RPM by changing/adjusting the drive.