Model VSU Make-Up Air

®

®

®

®

®

Heater Does Not Operate

Visible pilot

Troubleshooting

Flame signal greater

than 1.25 VDC

Measure the flame signal

when there is a visible pilot

Pressure drop across the burner

between 0.625 and 0.675 in. wc?

Check for proper airflow

(Direct Gas Start-Up Step #3)

Does the flame signal

remain constant?

Adjust burner baffles

(Reference Direct Gas Start-Up – Step #3)

If the signal slowly drops off, typically the airflow is too low

(Reference Blower Start-Up – Step #4)

If it suddenly drops to zero, the flame rod is grounding out

(Adjust the flame rod to avoid contact with the burner or the unit)

Adjust the minimum firing rate

(Reference Direct Gas Start-Up – Step #4)

Check the minimum firing rate

(Direct Gas Start-Up Step #4

Is the minimum firing rate

set correctly?

Note: When the pressure is low or marginal and the unit

begins heating, the air density will change. This can cause
the pressure to drop below the minimum setting. Also, low

airflow can cause the flame to walk out of the burner and

away from the flame sensor, causing the unit to recycle.

Yes

Yes

If the flame signal is above 1.25 VDC and constant,

the main gas valves will remain open until the call

for heat is interrupted or the unit is shut down.

No

Note: The flame signal should be steady and

above 1.25 VDC with a visible pilot.

(Reference Direct Gas Start-Up – Step #7)

Unit is not grounded

(Properly ground unit)

Flame rod is grounding out

(Adjust the flame rod to avoid contact with the burner or the unit)

Cracked porcelain on flame rod

(Replace flame rod)

No

Yes

Yes

No

No