SERVICING

41

DIPSWITCH FUNCTIONS

The MBE air handler motor has an electronic control that
contains an eight (8) position dip switch. The function of
these dipswitches are shown in Table 1.

D ipsw itch N um ber

Function

1
2
3

N /A

4

Indoor Therm ostat

5
6
7
8

Cooling & Heat Pum p CFM

CFM Trim Adjust

Electric H eat

Table 1

CFM DELIVERY

Tables 2, 2A and 3, 3A show the CFM output for dipswitch
combinations 1-2, 5-6 and 7-8.

Model

Switch 1

Switch 2

CFM

OFF

OFF

1,200

ON

OFF

1,000

OFF

ON

800

ON

ON

600

OFF

OFF

1,600

ON

OFF

1,400

OFF

ON

1,200

ON

ON

1,000

OFF

OFF

2,000

ON

OFF

1,800

OFF

ON

1,600

ON

ON

1,200

MBE1200

MBE1600

MBE2000

Electric Heat Operation

Table 2

Model

Switch 5

Switch 6

CFM

OFF

OFF

1,200

ON

OFF

1,000

OFF

ON

800

ON

ON

600

OFF

OFF

1,600

ON

OFF

1,400

OFF

ON

1,200

ON

ON

1,000

OFF

OFF

1,600

ON

OFF

1,400

OFF

ON

1,200

ON

ON

1,000

Cooling/Heat Pump Operation

MBE2000

MBE1200

MBE1600

Table 2A

Dipswitch 1/2 & 7/8
AEPF 1830

Heating

Element

(kw)

1

2

7

8

UP TO 10

OFF

OFF

OFF

OFF

1100

1210

UP TO 10

ON

OFF

OFF

OFF

890

935

5

OFF

ON

OFF

OFF

700

770

AEPF3036 / 3137 / 4260

Heating

Element

(kw)

1

2

7

8

UP TO 20

OFF

OFF

OFF

OFF

2050

2150

UP TO 20

ON

OFF

OFF

OFF

1750

1835

UP TO 15

OFF

ON

OFF

OFF

1600

1680

UP TO 10

ON

ON

OFF

OFF

1200

1260

UP TO 10

ON

ON

OFF

ON

1020

1070

Heat Pump

With Backup

Switch

Position

Switch

Position

Switch

Position

Switch

Position

Emergency

Backup

Heat Pump

With Backup

Emergency

Backup

Table 3

Dipswitch 5/6 & 7/8
AEPF 1830

5

6

7

8

Cooling

Heat Pump

OFF

OFF

OFF

OFF

1100

1100

ON

OFF

OFF

OFF

800

800

OFF

ON

OFF

OFF

600

600

5

6

7

8

Cooling

Heat Pump

OFF

OFF

OFF

OFF

1800

1800

ON

OFF

OFF

OFF

1580

1580

OFF

ON

OFF

OFF

1480

1480

ON

ON

OFF

OFF

1200

1200

ON

ON

OFF

ON

1020

1020

Switch

Position

Switch

Position

Indoor Airflow

Switch

Position

Switch

Position

Indoor Airflow

AEPF3036 / 3137 / 4260

Table 3A

THERMOSTAT “FAN ONLY” MODE

During Fan Only Operations, the CFM output is 30% of the
cooling setting.

CFM TRIM ADJUST

Minor adjustments can be made through the dip switch
combination of 7-8. Table 4 shows the switch position for
this feature.

NOTE: The airflow will not make the decreasing adjustment
in Electric Heat mode.

C FM

S w it c h 7

S w it c h 8

+ 1 0 %

O N

O F F

- 1 5 %

O F F

O N

Table 4