Servicing – Goodman Mfg RT6100004R13 User Manual

Page 47

Advertising
background image

SERVICING

47

AEP* & MBE WITH SINGLE STAGE CONDENSERS
When used with a single stage condenser, dip switch #4
must be set to the on position on the VSTB inside the MBE.
The “Y” output from the indoor thermostat must be connected
to the yellow wire labeled “Y/Y2” inside the wire bundle
marked “Thermostat” and the yellow wire labeled “Y/Y2”
inside the wire bundle marked “Outdoor Unit” must be
connected to “Y” at the condenser. The orange jumper wire
from terminal “Y1” to terminal “O” on the VSTB inside the
MBE must remain connected.

1.0 Cooling Operation

1.1 On a demand for cooling, the room thermostat energizes

“G” and “Y” and 24Vac is supplied to “G” and “Y/Y2” of the
MBE unit. The VSTB inside the MBE will turn on the
blower motor and the motor will ramp up to the speed
programmed in the motor based on the settings for dip
switch 5 and 6. The VSTB will supply 24Vac to “Y” at the
condenser and the compressor and condenser are turned
on.

1.2 When the cooling demand is satisfied, the room thermo-

stat removes the 24Vac from “G” and “Y”. The MBEand
AEP* remove the 24Vac from “Y’ at the condenser and the
compressor and condenser fan are turned off. The blower
motor will ramp down to a complete stop based on the
time and rate programmed in the motor.

2.0 Heating Operation

2.1 On a demand for heat, the room thermostat energizes

“W1” and 24Vac is supplied to terminal “E/W1” of the
VSTB inside the MBEand AEP* units. The VSTB will turn
on the blower motor and the motor will ramp up to the
speed programmed in the motor based on the settings for
dip switch 1 and 2. The VSTB will supply 24Vac to heat
sequencer HR1 on the electric heater assembly.

2.2 HR1 contacts M1 and M2 will close within 10 to 20

seconds and turn on heater element #1. At the same
time, if the heater assembly contains a second heater
element, HR1 will contain a second set of contacts, M3
and M4, which will close and turn on heater element #2.

Note: If more than two heater elements are on the heater

assembly, it will contain a second heat sequencer, HR2,
which will control the 3

rd

and 4

th

heater elements if

available. For the 3

rd

and 4

th

heater elements to

operate on a second stage heat demand, the PJ4
jumper on the VSTB inside the MBE and AEP* must
be cut.
With the PJ4 jumper cut, the VSTB will run the
blower motor on low speed on a “W1” only demand. If the
first stage heat demand, “W1” cannot be satisfied by the
heat pump, the temperature indoors will continue to drop.

The room thermostat will then energize “W2” and 24Vac
will be supplied to HR2 on the heater assembly and the
blower motor will change to high speed. When the “W2”
demand is satisfied, the room thermostat will remove the
24Vac from “W2” and the VSTB will remove the 24Vac
from HR2. The contacts on HR2 will open between 30 to
70 seconds and heater elements #3 and #4 will be turned
off and the blower motor will change to low speed. On
most digital/electronic thermostats, “W2” will re-
main energized until the first stage demand “W1” is
satisfied and then the “W1” and “W2” demands will
be removed.

2.3 When the “W1” heat demand is satisfied, the room

thermostat will remove the 24Vac from “E/W1” and the
VSTB removes the 24Vac from HR1. The contacts on
HR1 will open between 30 to 70 seconds and turn off the
heater element(s) and the blower motor ramps down to a
complete stop.

S-41A AEP* & MBE WITH SINGLE STAGE HEAT

PUMPS

When used with a single stage heat pump, dip switch #4 must
be set to the ON position on the VSTB inside the MBE. The
“Y” output from the indoor thermostat must be connected to
the yellow wire labeled “Y/Y2” inside the wire bundle marked
“Thermostat” and the yellow wire labeled “Y/Y2” inside the
wire bundle marked “Outdoor Unit” must be connected to “Y”
at the heat pump. The orange jumper wire from terminal
“Y1” to terminal “O” on the VSTB inside the MBE must
be removed.

3.0 Cooling Operation

On heat pump units, when the room thermostat is set to the
cooling mode, 24Vac is supplied to terminal “O” of the VSTB
inside the MBE unit. The VSTB will supply 24Vac to “O” at
the heat pump to energize the reversing valve. As long as the
thermostat is set for cooling, the reversing valve will be in the
energized position for cooling.

3.1 On a demand for cooling, the room thermostat energizes

“G” and “Y” and 24Vac is supplied to terminals “G” and “Y/
Y2” of the MBE unit. The VSTB will turn on the blower
motor and the motor will ramp up to the speed pro-
grammed in the motor based on the settings of dip switch
5 and 6. The VSTB will supply 24Vac to “Y” at the heat
pump.

3.2 The heat pump is turned on in the cooling mode.

3.3 When the cooling demand is satisfied, the room thermo-

stat removes the 24Vac from “G” and “Y/Y2” of the MBE
and the VSTB removes the 24Vac from “Y” at the heat
pump. The heat pump is turned off and the blower motor
will ramp down to a complete stop based on the time and

Advertising