Servicing – Goodman Mfg RT6100004R13 User Manual

Page 56

Advertising
background image

SERVICING

56

S-111 CAPILLARY TUBES/RESTRICTOR ORIFICES

The capillary tubes/restrictor orifices used in conjunction with
the indoor and outdoor coil, are a predetermined length and
bore (I.D.).

They are designed to control the rate of liquid refrigerant flow
into an evaporator coil.

The amount of refrigerant that flows through the capillary tube/
restrictor orifice is regulated by the pressure difference
between the high and low sides of the system.

In the cooling cycle when the outdoor air temperature rises,
the high side condensing pressure rises. At the same time,
the cooling load on the indoor coil increases, causing the low
side pressure to rise, but at a slower rate.

Since the high side pressure rises faster when the tempera-
ture increases, more refrigerant flows to the evaporator,
increasing the cooling capacity of the system.

When the outdoor temperature falls, the reverse takes place.
The condensing pressure falls, and the cooling loads on the
indoor coil decrease, causing less refrigerant flow.

A strainer is placed on the entering side of the tubes to prevent
any foreign material from becoming lodged inside the capil-
lary tubes.

If a restriction should become evident, proceed as follows:

1. Capture the refrigerant charge.

2. Remove the capillary tubes/restrictor orifice or tube strainer

assembly. and replace.

3. Replace liquid line drier, evacuate and recharge.

Capillary Tubes/Orifice Assembly

CHECKING EQUALIZATION TIME

During the "OFF" cycle, the high side pressure bleeds to the
low side through the capillary tubes/restrictor orifices. Check
equalization time as follows:

1. Attach a gauge manifold to the suction and liquid line dill

valves.

2. Start the system and allow the pressures to stabilize.

3. Stop the system and check the time it takes for the high

and low pressure gauge readings to equalize.

If it takes more than seven (7) minutes the capillary tubes/
restrictor orifices are inoperative. Replace, install a liquid line
drier, evacuate and recharge.

S-112 CHECKING RESTRICTED LIQUID LINE

When the system is operating, the liquid line is warm to the
touch. If the liquid line is restricted, a definite temperature
drop will be noticed at the point of restriction. In severe cases,
frost will form at the restriction and extend down the line in the
direction of the flow.

Discharge and suction pressures will be low, giving the
appearance of an undercharged unit. However, the unit will
have normal to high subcooling.

Locate the restriction, replace the restricted part, replace
drier, evacuate and recharge.

S-113 OVERCHARGE OF REFRIGERANT

An overcharge of refrigerant is normally indicated by an
excessively high head pressure.

An evaporator coil, using an expansion valve metering device,
will basically modulate and control a flooded evaporator and
prevent liquid return to the compressor.

An evaporator coil, using a capillary tube metering device,
could allow refrigerant to return to the compressor under
extreme overcharge conditions. Also with a capillary tube
metering device, extreme cases of insufficient indoor air can
cause icing of the indoor coil and liquid return to the compres-
sor, but the head pressure would be lower.

There are other causes for high head pressure which may be
found in the "Service Problem Analysis Guide."

If other causes check out normal, an overcharge or a system
containing non-condensables would be indicated.

If this system is observed:

1. Start the system.

2. Remove and capture small quantities of gas from the

suction line dill valve until the head pressure is reduced to
normal.

3. Observe the system while running a cooling performance

test. If a shortage of refrigerant is indicated, then the
system contains non-condensables.

S-114 NON-CONDENSABLES

If non-condensables are suspected, shut down the system
and allow the pressures to equalize. Wait at least 15
minutes. Compare the pressure to the temperature of the
coldest coil since this is where most of the refrigerant will be.
If the pressure indicates a higher temperature than that of the
coil temperature, non-condensables are present.

Non-condensables are removed from the system by first
removing the refrigerant charge, replacing and/or installing
liquid line drier, evacuating and recharging.

S-115 COMPRESSOR BURNOUT

When a compressor burns out, high temperature develops
causing the refrigerant, oil and motor insulation to decom-
pose forming acids and sludge.

If a compressor is suspected of being burned-out, attach a
refrigerant hose to the liquid line dill valve and properly remove
and dispose of the refrigerant.

Advertising