Roof Curb and Mounting Details

The figures below illustrates three common methods
used to install Vektor systems. Methods used to attach
a Vektor unit are dependent on local codes, roof
construction design and roof construction materials.
Consult an architect or structural engineer for proper
means of attachment.

Steel

Wood

Vektor-H

Concrete

Lifting Information

CAUTION

The cone is to be lifted by the cone lifting lugs,
separately and individually from the fan assembly.

NOTE

Steel, concrete or wood roof support is per structural
engineer and in accordance with load requirements
and applicable building codes.

STEEL STRUCTURAL SUPPORT
(BY OTHERS, SEE NOTE ABOVE)

Continuous weld or stitch weld.
Minimum 6 inch

(152.4 mm) stitch weld by

3.25 inch

(82.5 mm) spacing minimum.

Minimum 6 inch

(152.4 mm) weld on each corner.

OR

Install 5/16 inch

(7.9375 mm) 24 Dril-Flex® Self-Drilling

Tapping Screws. 3/16 inch

(4.7625 mm) minimum thread

engagement into A36 steel, centered in flange.
4.5 inch

(114.3 mm) spacing

5/8 inch

(15.875 mm) minimum edge distance

ALL HARDWARE BY OTHERS

Greenheck Roof Curb GPFHL/GPFHD

CONCRETE STRUCTURAL SUPPORT
(BY OTHERS, SEE NOTE ABOVE)

Install 3/8 inch

(9.525 mm) SS power wedge bolts

2.5 inch

(63.5 mm) maximum spacing from curb corners

4.5 inch

(114.3 mm) maximum bolt spacing

3.5 inch

(88.9 mm) minimum embedment

4.5 inch

(114.3 mm) minimum edge

distance centered in flange
ALL HARDWARE BY OTHERS

Greenheck Roof Curb GPFHL/GPFHD

WOODEN STRUCTURAL SUPPORT
(BY OTHERS, SEE NOTE ABOVE)

Greenheck Roof Curb GPFHL/GPFHD

Install 3/8 inch

(9.525 mm) SS lag or thru-bolt with

1 inch

(25.4 mm) O.D. washer

2.5 inch

(63.5 mm) maximum spacing from curb corners

4.5 inch

(114.3 mm) maximum bolt spacing

3.5 inch

(88.9 mm) minimum tread engagement,

not including tapered tip
2 inch

(50.8 mm) minimum edge distance,

centered in flange
Pre-drill holes 40-60% of lag diameter
ALL HARDWARE BY OTHERS

Single Fan System

without Bypass Air Plenum

Single Fan System

with Bypass Air Plenum

Cone

Lifting Lugs

Bypass

Air

Plenum

Fan

Cone

Unit

Assembly

Lifting Lugs

Multiple Fan System with Bypass Air Plenum

Cone

Lifting Lugs

Unit

Assembly

Lifting Lugs

Unit

Assembly

Lifting Lugs

Cone

Lifting Lugs

Vektor-HS with SAVVE Technology

4

Laboratory Exhaust System

®