Plenum drainage piping / trap detail (by others), Electrical connections, Positive pressure trap on tubular fan housing – Greenheck Fan Laboratory Exhaust System Vektor-HS User Manual

Page 7: Negative pressure trap on bypass air plenum, Fan drain connection plenum drain connection, Single phase layout, Three phase layout, Three phase with variable frequency drives layout

Advertising
background image

Plenum Drainage Piping / Trap
Detail (By Others)

There is a location for a pipe connection on each tubular
fan housing and bypass air plenum. Each drain may
need to be connected to a drainage system to ensure
proper disposal of any water or condensate that may
occur.

• Drain connections are 0.5 inch NPT

Installed piping to have a downward angle to allow
for drainage

Fill traps to recommended level before start-up

Note: A conservative method of trap design is to set N

= total static pressure.

Positive Pressure Trap on Tubular Fan Housing

Fan Drain

Connection

Plenum Drain

Connection

Negative Pressure Trap on Bypass Air Plenum

N = Negative fan pressure (inches W.C.)
H = N - (0.5 inches minimum

H/2

H/2

H

1.25 inch minimum

N

FAN ON

FAN OFF

N = Negative fan pressure (inches W.C.)
H = N - (0.5 inches minimum)

H/2

H/2

H

1.25 inch
minimum

N

FAN ON

FAN OFF

Connect
this end
to fan drain.

Before electrical connections are made, the supply
voltage, phase and ampere capacity must be checked

Electrical Connections

NOTE

Refer to the Vektor-HS SAVVE controls
Installation, Operation and Maintenance Manual
for electrical wiring and connection information.

Single Phase Layout

LINE IN

115/208/230/277 volt, single phase

MOTOR

DISCONNECT

115/208/230/277 volt

Single phase

TRANSFORMER

208/230/277 volt, single phase

Transformers must be wired independent

from VFD control.

24/115 volt, single phase

isolation damper actuator motor

power open/spring close

115/208/230/277 volt

Single phase

Disconnect is mounted to fan housing

Optional transformer and isolation damper, refer to CAPS file selection

Field Wiring
Factory Wiring

Three Phase Layout

LINE IN

208/230/460/575 volt, three phase

MOTOR

DISCONNECT

208/230/460/575 volt

Three phase

TRANSFORMER

208/230/460/575 volt, single phase

Transformers must be wired independent

from VFD control.

24/115 volt, single phase

isolation damper actuator motor

power open/spring close

208/230/460/575 volt

60 cycle, three phase

Disconnect is mounted to fan housing

Optional transformer and isolation damper, refer to CAPS file selection

Field Wiring
Factory Wiring

Three Phase with

Variable Frequency Drives Layout

LINE IN

208/230/460/575 volt, three phase

MOTOR

DISCONNECT

208/230/460/575 volt

Three phase

VFD

supplied and wired

by others

TRANSFORMER (if required)

208/230/460/575 volt, single phase

Transformers must be wired independent

from VFD control.

24/115 volt, single phase

isolation damper actuator motor

power open/spring close

208/230/460/575 volt

60 cycle, three phase

Disconnect is mounted to fan housing

Optional transformer and isolation damper,
refer to CAPS file selection

Field Wiring
Factory Wiring

for compatibility with the fan motor. In addition, the
supply wiring must be properly fused and conform to
local and national electrical codes. If the unit is supplied
with a safety disconnect switch, ensure proper wiring
to the fan motor. Be sure the disconnect is switched to
the “OFF” position before connecting supply wires. If
no disconnect is supplied, ensure the supply wire is not
live before connection. Supply wires are then connected
to the optional safety disconnect switch (if supplied) or
motor.

Vektor-H Motor Disconnect and Isolation Damper
Wiring Diagram

Disconnect is mounted to fan housing. Transformers are
mounted to bypass air plenum with damper actuator
motors. For systems that ship unassembled because
of physical size, this connection at disconnect from
transformers must be field-installed. Wires with conduit
and fittings are provided pre-connected to transformers.

7

Laboratory Exhaust System

®

Advertising
This manual is related to the following products: