305mm x 305mm

Velocity

(m/s)

Pressure

Drop (Pa)

2.5

13

5

55

7.5

122

10.2

222

12.7

349

15.4

508

17.9

688

20.6

907

610mm x 610mm

Velocity

(m/s)

Pressure

Drop (Pa)

2.5

8

5

35

7.6

75

10.3

140

12.8

217

15.3

309

17.7

409

20.8

568

914mm x 914mm

Velocity

(m/s)

Pressure

Drop (Pa)

2.5

8

5.1

30

7.7

67

10.2

115

12.9

184

15.5

269

18.1

354

20.6

471

305mm x 1219mm

Velocity

(m/s)

Pressure

Drop (Pa)

2.6

8

5.1

32

7.7

75

10.2

130

12.7

202

15.5

301

18.1

416

20.6

536

1219mm x 305mm

Velocity

(m/s)

Pressure

Drop (Pa)

2.5

1

5

42

7.7

95

10.3

172

12.7

264

15.3

381

17.9

521

20.8

707

AMCA 5.5 Pressure Drop

FSD-M211

5D

6D

5D

D

4 (W) (H)

3.14

2

5

10

30

10

100

1000

305mm x 305mm

610mm x 610mm

914mm x 914mm

305mm x 1219mm

1219mm x 305mm

PRESSURE DROP- P

ASCALS

FACE VELOCITY- METERS/SECOND

AMCA 5.5

VELOCITY VS. PRESSURE DROP

305 x 305 1219 x 305

610 x 610

305 x 1219
914 x 914

R

Greenheck Kunshan Co. Ltd. and Greenheck

Fan Corporation certifies that the model FSD-

M211 shown herein is licensed to bear the AMCA

Seal. The ratings shown are based on tests and

procedures performed in accordance with AMCA

Publication 511 and comply with the requirements

of the AMCA Certified Ratings Programs. The AMCA

Certified Ratings Seal applies to air performance

ratings only.