24 v, 115 v – Goodman Mfg GHS8 User Manual

Page 16

Advertising
background image

16

IO-242C

05/05

WARNING

T

O AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR DEATH, THE FURNACE

MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR,

IN THEIR ABSENCE, WITH THE LATEST EDITION OF THE

N

ATIONAL

E

LECTRIC

C

ODE.

To ensure proper unit grounding, the ground wire should run
from the furnace ground screw located inside the furnace junction
box all the way back to the electrical panel. NOTE: Do not use
gas piping as an electrical ground. To confirm proper unit
grounding, turn off the electrical power and perform the following
check.

1. Measure resistance between the neutral (white)

connection and one of the burners.

2. Resistance should measure 10 ohms or less.

This furnace is equipped with a blower door interlock switch
which interrupts unit voltage when the blower door is opened for
servicing. Do not defeat this switch.

24 V

OLT

T

HERMOSTAT

W

IRING

NOTE: Wire routing must not interfere with circulator blower
operation, filter removal, or routine maintenance.

Low voltage connections can be made through either the right or
left side panel. Thermostat wiring entrance holes are located in
the blower compartment. The following figure shows
connections for a “heat only” system and “heat/cool system”.

Y

R

C

Y

R

C

G

W

Y

C

Furnace
Control

Furnace
Control

Remote

Condensing

Unit

Heating
Room Thermostat

Heating/Cooling
Room Thermostat

G

W

G

W

C

Y

R

R

W

Typical Field Wiring (24 VAC Control Circuit)

This furnace is equipped with a 40 VA transformer to facilitate
use with most cooling equipment. Consult the wiring diagram,
located on the blower compartment door, for further details of
115 Volt and 24 Volt wiring.

A single-stage thermostat with only one heating stage can be
used to control this furnace.

S

ETTING

THE

H

EAT

A

NTICIPATOR

The following method should be used in measuring the amp
draw of the control circuit to assure proper adjustment of the
thermostat heat anticipator

R

R

• Wrap the “R” leg around a clip-on amp meter 10 times.
• Energize the furnace in the heat mode.
• Record the reading.
• Divide this reading by 10.
• Set the heat anticipator on the thermostat to match this

reading.

Example: If the reading on the amp meter is “4”, divide this by 10.
The anticipator setting will be .4 amps.

115 V

OLT

L

INE

C

ONNECTION

OF

A

CCESSORIES

(H

UMIDIFIER

AND

E

LECTRONIC

A

IR

C

LEANER

)

WARNING

T

O AVOID PERSONAL INJURY, ELECTRICAL SHOCK OR DEATH, DISCONNECT

ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL

WIRING.

The furnace integrated control module is equipped with line
voltage accessory terminals for controlling power to an optional
field-supplied humidifier and/or electronic air cleaner.

The accessory load specifications are as follows:

Humidifier

1.0 Amp maximum at 120 VAC

Electronic Air Cleaner

1.0 Amp maximum at 120 VAC

Turn OFF power to the furnace before installing any accessories.
Follow the humidifier or air cleaner manufacturers’ instructions
for locating, mounting, grounding, and controlling these
accessories. Accessory wiring connections are to be made
through the 1/4" quick connect terminals provided on the furnace
integrated control module. The humidifier and electronic air
cleaner hot and neutral terminals are identified as HUM and EAC.
All field wiring must conform to applicable codes. Connections
should be made as shown in the following illustration.

EA

C

Li

ne

T

ran

s

for

me

r

Hu

m

Li

ne

T

ran

s

for

me

r

EA

C

Hu

m

Air Cleaner

Humidifier

Control Module

Hot 120 VAC

Neutral 120 VAC

Optional

Accessories

{

If it is necessary for the installer to supply additional line voltage
wiring to the inside of the furnace, the wiring must conform to all
local codes, and have a minimum temperature rating of 105°C.
All line voltage wire splices must be made inside the furnace
junction box.

The integrated control module humidifier terminals (HUM) are
energized with 115 volts whenever the induced draft blower is
energized. The integrated control module electronic air cleaner
terminals (EAC) are energized with 115 volts whenever the
circulator blower is energized.