Roubleshooting, Hart – Goodman Mfg GHS8 User Manual

Page 30

Advertising
background image

30

IO-242C

05/05

T

ROUBLESHOOTING

C

HART

Fault Description(s)

Symptoms of Abnormal

Operation

4

4 FLASHES

Associated

LED Code

2

• Circulator blower runs

continuously. No furnace
operation.

• Integrated control module

diagnostic LED is flashing
FOUR (4) flashes.

6

6 FLASHES

7

7 FLASHES

• Furnace fails to operate.

• Integrated control module

diagnostic LED is flashing
SIX (6) flashes.

• Normal furnace

operation.

• Integrated control

module diagnostic LED
is flashing SEVEN (7)
flashes.

• Rollout limit

open.

• Flame sense

microamp signal is
low.

• Insufficient conditioned air

over the heat exchanger.
Blocked filters, restrictive
ductwork, improper
circulator blower speed,
or failed circulator blower.

Possible Causes

Corrective Action

Cautions and Notes

• Check filters and

ductwork for blockage.
Clean filters or remove
obstruction.

• Check circulator blower

speed and performance.
Correct speed or replace
blower if necessary.

• Turn power OFF

prior to repair.

• See Product

Data Bulletin for
allowable rise
range and proper
circulator speed.

• Flame sensor is coated/

oxidized.

• Flame sensor incorrectly

positioned in burner
flame.

• Lazy burner flame due to

improper gas pressure or
combustion air.

• Sand flame sensor is

coated/oxidized.

• Inspect for proper sensor

alignment.

• Check inlet air piping for

blockage, proper length,
elbows, and termination.

• Compare current gas

pressure to rating plate
info. Adjust as needed.

• Turn power OFF

prior to repair.

• Clean flame

sensor with steel
wool.

• See “Vent/Flue

Pipe” section for
piping details.

• See rating plate

for proper gas
pressure.

• See “Vent/Flue

Pipe” section for
piping details.

• Replace induced

draft blower with
proper
replacement part.

• Primary limit

circuit is open.

• Induced draft blower runs

continuously. No furnace
operation.

• Integrated control module

diagnostic LED is flashing
continuously.

C

CONTINUOUS

FLASHING

• Polarity of 115

volt power is
reversed.

• Polarity of 115 volt AC

power to furnace or
integrated control module
is reversed.

• Poor unit ground.

• Review wiring diagram to

correct polarity.

• Verify proper ground.

Correct if necessary.

• Check and correct wiring.

• Turn power OFF

prior to repair.

2

LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.

3

Applies to GMS8/GDS8/GHS8 Models only.

• Normal operation.

• LED is steady on

steady on

• Check burners for

proper alignment.

• Check flue and air inlet

piping for blockage,
proper length, elbows,
and termination.
Correct as necessary.

• Check induced draft

blower for proper
performance.
Replace, if necessary.

• Tighten or correct

wiring connection.

• Flame rollout.

• Misaligned burners,

blocked flue and/or air
inlet pipe, or failed
induced draft blower.

• Loose or improperly

connected wiring.

• Induced draft blower and

circulator blower runs
continuously. No furnace
operation.

• Integrated control module

diagnostic LED is flashing
FIVE (5) flashes.

5

5 FLASHES

• Flame sensed

with no call for
heat.

• Short to ground in flame

sense circuit.

• Correct short at flame

sensor or in flame
sensor wiring

• Turn power OFF

prior to repair.