Goodman Mfg GHS8 User Manual

Page 7

Advertising
background image

7

IO-242C

05/05

Refer to subbase instructions for installation details.
Follow the instructions with the subbase for proper
installation. Do not install the furnace directly on carpeting,
tile, or other combustible material other than wood flooring.
(Note: The subbase will not be required if an air
conditioning coil is installed between the supply air opening
on the furnace and the floor.)

Top - 1"

Side

Clearance - 1"

Back - 0"

Front Clearance - 3"

Vent Pipe Clearance to Combustibles-
6" using Single Wall Connector or 1"
using B-1 vent.

• Adequate combustion/ combustion air must be supplied

to the closet.

• Furnace must be completely sealed to floor or base.

Combustion/ ventilation air supply pipes must terminate
12" from top of closet and 12" from floor of closet. DO NOT
remove solid base plate for side return.

• Return air ducts must be completely sealed to the furnace

and terminate outside the enclosure surfaces.

C

LEARANCES

AND

A

CCESSIBILITY

Unobstructed front clearance of 24" for servicing is
recommended.

T O P

B1-V EN T

SIN G LE

(P LEN U M )

1"

6"

1"

3"

0"

1"

VE N T

SID ES

FR O N T

B AC K

Top clearance for horizontal configuration - 1"

H

ORIZONTAL

I

NSTALLATION

Line contact to framing is permitted when installed in the horizontal
configuration. Line contact is defined as the portion of the cabinet
that is formed by the intersection of the top and side.
ACCESSIBILITY CLEARANCE,WHERE GREATER, SHOULD TAKE
PRECEDENCE OVER MINIMUM FIRE PROTECTION
CLEARANCE. A gas-fired furnace for installation in a residential
garage must be installed so that the ignition source and burners
are located not less than eighteen inches (18") above the floor
and is protected or located to prevent physical damage by vehicles.
A gas furnace must not be installed directly on carpeting, tile, or
other combustible materials other than wood flooring.

F

URNACE

S

USPENSION

If suspending the furnace from rafters or joist, use 3/8" threaded
rod and 2”x2”x3/8” angle iron as shown below. The length of rod
will depend on the application and the clearances necessary.

TILT OUTWARD TO ALLOW FOR

DOOR AND CIRCULATOR BLOWER

REMOVAL

3/8" DIAMETER

THREADED ROD

(6 PLACES)

PROVIDE 8" MINMUM CLEARANCE BETWEEN

CENTER ROD AND FURNACE CABINET

TO ALLOW FOR CIRCULATOR BLOWER REMOVAL

ASSURE FURNACE IS LEVEL FROM

END TO END AND HAS A SLIGHT

FORWARD TILT WITH THE FRONT

OF THE FURNACE 0"-3/4"

BELOW THE BACK OF THE FURNACE

POSITION AS CLOSE AS POSSIBLE

TO BLOWER DECK TO ALLOW FOR

CIRCULATOR BLOWER REMVOAL

HOLD DOWN

NUTS

SUPPORT

NUTS

2" X 2" X 3/8"

A

NGLE

I

RON

(3 PLACES)

Suspended Furnace

E

XISTING

F

URNACE

R

EMOVAL

NOTE: When an existing furnace is removed from a venting system
serving other appliances, the venting system may be too large to
properly vent the remaining attached appliances.

The following vent testing procedure is reproduced from the
American National Standard/National Standard of Canada for
Gas-Fired Central Furnaces ANSI Z21.47-1998, CSA-2.3-M98
Section 1.23.1.
The following steps shall be followed with each
appliance connected to the venting system placed in operation,
while any other appliances connected to the venting system are
not in operation:

a. Seal any unused openings in the venting system;
b. Inspect the venting system for proper size and horizontal

pitch, as required by the National Fuel Gas Code, ANSI
Z223.1 or the CAN/CSA B149 Installation Codes and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition;

c. In so far as practical, close all building doors and windows

and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building. Turn on clothes dryers and any
appliance not connected to the venting system. Turn on any
exhaust fans, such as range hoods and bathroom exhausts,
so they shall operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers;

d. Follow the lighting instructions. Place the appliance being

inspected in operation. Adjust thermostat so appliance shall
operate continuously;

e. Test for draft hood equipped appliance spillage at the draft

hood relief opening after 5 minutes of main burner operation.
Use the flame of a match or candle;

f. After it has been determined that each appliance connected

to the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, fireplace
dampers and any other gas burning appliance to their
previous conditions of use;

g. If improper venting is observed during any of the above

tests, the common venting system must be corrected.

Advertising