Heat kit electrical data, 7½ t, Lectrical – Goodman Mfg CPH COMMERCIAL SS-CPH90-150 User Manual

Page 20

Advertising
background image

20

www.goodmanmfg.com

SS-CPH90-150

SS-CPH90-150

www.goodmanmfg.com

21

P

roduct

S

PecificationS

P

roduct

S

PecificationS

H

eat

k

it

e

leCtriCal

d

ata

— 7½ t

ons

m

inimum

a

irflow

for

e

leCtriC

H

eat

Heater Size (kW)

Minimum CFM

15

3,000

30

3,000

43

3,000

Model and

Heat Kit Usage

MCA¹

at 208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

CPH090***3B***

40

50

EHK3-16

74 / 85

80 / 90

15

3000-3375 CFM

EHK3-30

113 / 130

120 / 150

30

3000-3375 CFM

EHK3-45

147 / 169

150 / 175

43

3000-3375 CFM

Model and

Heat Kit Usage

MCA¹

at 208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

CPH090***4B***

19

25

EHK4-16

42

45

15

3000-3375 CFM

EHK4-30

64

70

30

3000-3375 CFM

EHK4-45

84

90

43

3000-3375 CFM

Model and

Heat Kit Usage

MCA¹

at 208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

CPH090***7B***

14

15

EHK4-16

32

35

15

---

EHK4-30

51

60

30

---

EHK4-45

68

70

43

---

¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device

k

w C

orreCtion

f

aCtor

kW Correction Factor for 1- & 3-Phase Units

Supply Voltage

240

230

220

210

208

Correction Factor

1

0.93

0.82

0.78

0.76

kW Correction Factor for 480V Units

Supply Voltage

460

440

430

Correction Factor

0.92

0.84

0.8

For other voltage, use voltage² / 480²

kW Correction Factor for 575V Units

Supply Voltage

560

550

540

Correction Factor

0.95

0.91

0.88

Multiply rated kW by correction factor to get actual kW.