10 t, Lectrical – Goodman Mfg CPH COMMERCIAL SS-CPH90-150 User Manual

Page 22

Advertising
background image

22

www.goodmanmfg.com

SS-CPH90-150

SS-CPH90-150

www.goodmanmfg.com

23

P

roduct

S

PecificationS

P

roduct

S

PecificationS

H

eat

k

it

e

leCtriCal

d

ata

— 10 t

ons

k

w C

orreCtion

f

aCtor

kW Correction Factor for 1- & 3-Phase Units

Supply Voltage

240

230

220

210

208

Correction Factor

1

0.93

0.82

0.78

0.76

kW Correction Factor for 480V Units

Supply Voltage

460

440

430

Correction Factor

0.92

0.84

0.8

For other voltage, use voltage² / 480²

kW Correction Factor for 575V Units

Supply Voltage

560

550

540

Correction Factor

0.95

0.91

0.88

Multiply rated kW by correction factor to get actual kW.

m

inimum

a

irflow

for

e

leCtriC

H

eat

Heater Size (kW)

Min. CFM

Down-shot

Min. CFM

Horizontal

15

4,000

4,000

30

4,000

4,000

43

4,000

4,000

Model and

Heat Kit Usage

MCA¹ at

208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

CPH120***3B/V***

49

60

EHK3-16

81 / 94

90 / 100

15

3500 - 4500 CFM

EHK3-30

122 / 139

125 / 150

35

3500 - 4500 CFM

EHK3-45

154 / 178

175 / 200

43

4000 - 4500 CFM

Model and

Heat Kit Usage

MCA¹

at 480V

MOP² (amps)

at 480V

Actual kW

at 480V

Recommended

Airflow Range

CPH120***4B/V***

24

30

EHK4-16

46

50

15

3500 - 4500 CFM

EHK4-30

69

70

30

3500 - 4500 CFM

EHK4-45

89

90

43

4000 - 4500 CFM

Model and

Heat Kit Usage

MCA¹

at 575V

MOP² (amps)

at 575V

Actual kW

at 575V

Recommended

Airflow Range

CPH0120***7B/V***

17

20

EHK7-16

36

40

15

3500 - 4500 CFM

EHK7-30

55

60

30

3500 - 4500 CFM

EHK7-45

71

80

43

4000 - 4500 CFM

¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device

Advertising