Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit
operation. Leave a total clearance of 75” on the main control panel side of the unit for possible removal
of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48” on all other sides of the unit for
possible compressor removal or service access, and to ensure proper
ventilation and condenser airflow. Do not install the unit beneath
any obstruction. Install the unit away from all building
exhausts to inhibit ingestion of exhaust air into the unit’s
fresh-air intake.