— 12½ t

ons

kW Correction Factor for 1- & 3-Phase Units

Supply Voltage

240

230

220

210

208

Correction Factor

1

0.93

0.82

0.78

0.76

kW Correction Factor for 480V Units

Supply Voltage

460

440

430

Correction Factor

0.92

0.84

0.8

For other voltage, use voltage² / 480²

kW Correction Factor for 575V Units

Supply Voltage

560

550

540

Correction Factor

0.95

0.91

0.88

Multiply rated kW by correction factor to get actual kW.

kw C

orreCtion

f

aCtors

Model and

Heat Kit Usage

MCA¹ at

208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

CPH150***3B***

65

80

EHK3-16

110

110

15

4000 - 5600

EHK3-30

155

175

30

4300 - 5600

EHK3-45

194

200

43

4500 - 5600

Model and

Heat Kit Usage

MCA¹ at

208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

CPH150***4B***

31

40

EHK4-16

54

60

15

4000 - 5600

EHK4-30

76

80

30

4300 - 5600

EHK4-45

96

100

43

4500 - 5600

Model and

Heat Kit Usage

MCA¹ at

208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

CPH150***7B***

23

30

EHK7-16

42

45

15

4000 - 5600

EHK7-30

61

70

30

4300 - 5600

EHK7-45

77

80

43

4500 - 5600

¹ Minimum Circuit Ampacity (standard drive)
² Maximum Overcurrent Protection device (standard drive)