Pre-installation checks, Brunel 1a brunel 2cb brunel 3cb, Flue 2. additional ventilation – Stovax 7008Bl User Manual

Page 17

Advertising
background image

17

PRe-INsTAllATIoN CHeCKs

Model
Brunel 1a - 7008/7008BL/7008LG
Brunel 2CB - 7051/7051BL/7051LG
Brunel 3CB - 7053/7053BL/7053LG

Flue/Chimney size

Flue/Chimney Minimum Height*

Without Liner System Round (diameter)

mm

150

150

150

6

6

6

135

135

135

5

1

/

2

5

1

/

2

5

1

/

2

150†

150

150

6†

6

6

4

4

4

13

13

13

inch

mm

inch

mm

inch

m

feet

Without Liner System (square) minimum

dimension

With Liner or Factory made System

(diameter)

installed in accordance with manufacturers instructions

Brunel

1a

Brunel

2CB

Brunel

3CB

*When measured from the top of the stove to the top of the flue, with no horizontal sections

and a maximum of 4 bends with angles of less than 45°

‡ May be 125mm (5”) if burning low volatiles (smokeless) fuels approved for use in Smoke Control Areas.

See web site http://uksmokecontrolareas.co.uk for more information about approved fuels.

1. FlUe

2. AddITIoNAl VeNTIlATIoN

2.1 Additional ventilation is required to comply with the

requirements of the Building Regulations. This must be

provided using a permanently open air vent, of the size

listed, which is positioned so that it is not liable to be

blocked both inside and outside the building.

2.2 Extractor fans or cooker hoods must not be placed in the

same room or space as this can cause the appliance to emit

fumes into the room.

2.3 If any of these checks reveal problems do not proceed

with the fitting of the appliance until they have been

rectified.

Model
Brunel 1a - 7008/7008BL/7008LG
Brunel 2CB - 7051/7051BL/7051LG
Brunel 3CB - 7053/7053BL/7053LG

Brunel

1a

Brunel

2CB

Brunel

3CB

Additional Ventilation

mm

2

0

550 1100

cm

2

0

5.5

11.0

In

2

0

0.85

1.7