Option 13: dtmf dialing, Range = on/off (default = on), Press add or delete – GE 60-883-95R User Manual

Page 17: Press option, Press 1, then 3, Press done, Option 14: auto phone test, Range = off, 001-254 days (default = off), Press add, Press 1, then 4

Advertising
background image

Programming Options

12

Option 13: DTMF Dialing

Range = On/Off (Default = On)

Determines whether the panel uses DTMF (on) or pulse (off) for dialing pro-

grammed phone numbers.

¾

To Add or Delete DTMF Dialing:

1. Press Add or Delete.
2. Press Option #.
3. Press 1, then 3.
4. Press Done.

Option 14: Auto Phone Test

Range = Off, 001-254 days (Default = Off)

Determines whether the panel automatically performs a periodic phone test.
The test interval can be from 001 to 254 days. Entries must be 3 digits. The

time of day the panel performs the test is determined by Option 32: Supervi-

sory Time, which must be turned on for this feature to work.

Note

Auto Phone Test must be set to 001 for ETL (UL 1635) listed systems.

¾

To program Auto Phone Test:

1. Press Add.
2. Press Option #.
3. Press 1, then 4.
4. Enter the desired Auto Phone Test days

using the numbered buttons.

5. Press Done.

Option 15: RF Timeout

Range = 02-24 hours (Default = 12 hours)

Determines the time period within which the panel must receive at least one

supervisory signal from a learned sensor before identifying a sensor failure

for that sensor and sounding trouble beeps. Any sensor failure is reported

immediately and again at the supervisory time (Option 32: Supervisory

Time). See “Sensor Supervisory Failure” in the System Operation section

for more information.
The Timeout can be set from 02 to 24 hours. Entries must be 2 digits.

Note

Setting this feature to 2 hours may cause false reports.

RF Timeout must be set to 4 hours for ETL (UL 1635) listed systems.

¾

To program Auto Phone Test:

1. Press Add.
2. Press Option #.
3. Press 1, then 4.
4. Enter the desired Auto Phone Test days

using the numbered buttons.

5. Press Done.

Option 16: Manual Phone Test

Range = On/Off (Default = On)

Determines whether the user can perform a manual phone test to verify com-

munication to a central station/pager (on), or not (off).

¾

To Add or Delete Manual Phone Test:

1. Press Add or Delete.
2. Press Option #.
3. Press 1, then 6.
4. Press Done.

Option 17: AC Power Failure Report

Range = Off, 0-254 Min (Default = 60 Min)

Determines whether the panel sends AC Power failure reports to a central

station or pager after the programmed time period expires (on), or not (off).
After 30 seconds without AC Power the panel lights turn off. When the

panel is without AC Power for the programmed time, an AC power failure is

reported. The AC Power Failure Report time period can be set from 5 to 254

minutes. Entries must be 3 digits. The panel reports an AC power restoral

when AC power returns to the panel.

Note

AC Power Failure Report must be set to 15 minutes for ETL listed systems.

¾

To program an AC Power Failure Report

Time:

1. Press Add.
2. Press Option #.
3. Press 1, then 7.
4. Enter the desired AC Power Failure Report

Time in minutes using the numbered but-

tons.

5. Press Done.

Advertising