Premium ceiling fan, Dimensional data performance data – Greenheck Fan CSP User Manual

Page 16

Advertising
background image

PREMIUM CEILING FAN

A

SP

Dimensional Data

Performance Data

Performance certified is for Model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed
(RPM) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated
per AMCA Standard 301. Values are for installation type B: free inlet fan sone levels.

HVI CFM/Static Pressure in inches of WG

Model RPM

Amps

Watts

Sones

0.000 0.100 0.125 0.250 0.375 0.500 0.625 0.750 1.000

CFM 76

51

47

30

SP-A50

700

0.31

18

0.7

Sones 0.7

1.0

1.1 1.8

CFM 83

70

66

42

SP-A70

850

0.27

20

0.8

Sones 1.1

1.1

1.4 2.2

CFM 99

88

84

61

25

SP-A90

900

0.34

29

1.0

Sones 1.1

1.4

1.4 1.7

1.9

CFM 119 110 106 88

SP-A110

950

0.58

49

0.8

Sones 1.3

1.2

1.2 1.6

CFM 135 123 121 104

SP-A125

1100

0.62

53

1.2

Sones 1.4

1.7

1.8 1.9

CFM 216 197 192 167 133

SP-A190

1400

1.30

113

2.0

Sones 3.2

2.8

2.9 3.1

3.4

CFM 247 225 220 196 172 142 105

67

SP-A200

900

0.43

48

2.0

Sones

2.0 2.3 2.4 3.0 3.5 4.1 4.6 4.5

CFM 272 251 246 227 210 185 157 119

SP-A250 1000 0.77 83 2.0

Sones

2.9 3.0 3.0 3.4 4.4 4.6 4.9 5.2

CFM 315 293 287 257 231 207 175 124

SP-A290 1050 0.72 81 2.5

Sones

3.2 3.3 3.3 3.6 3.9 4.1 4.5 5.5

CFM 410 395 391 368 345 325 307 279

SP-A390 1350 1.34 135 4.5

Sones

5.4 5.4 5.4 5.7 6.0 6.3 6.4 6.7

CFM 443 413 405 351 305

SP-A410 1000 1.74 121 3.0

Sones 4.1

3.8

3.7 3.7

4.3

CFM 557 512 501 439 392 325

SP-A510 1070 3.30 224 4.5

Sones 6.0

5.7

5.6 5.5

5.4

4.7

CFM 757 729 723 700 679 649 613 560 396

SP-A700 1100 3.20 350 5.5

Sones

6.1 6.1 6.1 6.3 6.7 7.1 7.3 7.5 7.7

CFM 752 714 701 653 588 485 320

SP-A710 1080 4.40 285 6.0

Sones 7.4

7.2

7.2 7.0

6.8

6.7 6.7

CFM 812 782 775 741 704 665 625 581

SP-A780 1600 3.30 348 8.5

Sones

10.2

10.2

10.2 9.9 9.5 9.5 9.4 9.4

CFM 955 907 896 841 773 701

SP-A900 950 4.00 285 4.5

Sones 5.2

5.7

5.8 6.1

6.2

6.2

CFM 1125 1059 1043 964 885 796 662

SP-A1050

1095 6.30 420 6.0

Sones 7.2

7.0

6.9 6.8

6.6

6.5 6.5

CFM 1455 1414 1404 1353 1307 1262 1218 1174

SP-A1410

1450 7.40 786 9.5

Sones

11.6 11.6 11.7 11.6 11.5 11.6 11.6 11.6

CFM 1607 1568 1558 1506 1449 1407 1369 1323

SP-A1550

1610 8.60 818 10.0

Sones

12.4 12.1 12.1 12.0 11.9 12.8 14.1 15.9

Outlet connection width is 1 inch - Mounting bracket width is 1½

inch.

For complete dimensional information, see CAPS submittal drawings.
All dimensions are in inches.

A

B

C

D

E

1 HVI sones at 0.1 wg
2 Available with light

5 UL Listed for use above tubs.
6 Available with 277 volt motor.

3 Available with CRD - Ceiling Radiation Damper
4 Available with 50 Hz motors

(See CAPS for performance)

2,3,5,6

3,4

3

3

3

3

3

3,4,5

3,5

1

3,4

3,5

3,4,5,6

3,4,5

3,4

3,4

2,3,4,5,6

2,3,5

2,3,5

2,3,5

Standard Decorative

Unit

Model

A B C D

E

Grille

Grille Wt.

50, 70, 90

13

1

/

4

10

5

/

8

11

5

/

8

6

DIA.

14

7

/

8

x 13

1

/

4

15

1

/

4

sq.

12

110, 125, 190

13

1

/

4

10

5

/

8

10

1

/

2

8 6

14

7

/

8

x 13

1

/

4

15

1

/

4

sq.

17

200, 250, 290, 390

14

11

7

/

8

11

1

/

4

8 8

14

7

/

8

x 13

1

/

4

15

1

/

4

sq.

24

410,

510

18

14

3

/

8

14

1

/

2

8

8

19

3

/

8

x 16

3

/

8

- 31

700

23

5

/

8

11

5

/

8

11

5

/

8

19

1

/

2

8

25

1

/

8

x 13

1

/

2

- 34

710,

780

18

14

3

/

8

14

1

/

2

10

8

19

3

/

8

x 16

3

/

8

- 34

900, 1050, 1410, 1550 23

3

/

4

14

3

/

8

14

1

/

2

18

3

/

4

8

25 x 16

3

/

8

- 56

A

B

C

D

E

®

16

Advertising
This manual is related to the following products:

SP