Model VSU Make-Up Air

®

Set-Up Optional Components

Adjust the settings on the optional components. See
the unit’s specific wiring diagram located on the access
door or the unit.

• Heating Inlet Air Sensor

Typical setting: 60-70ºF

• Building Freeze Protection

Typical setting: 5 minutes; 45ºF

• Dirty Filter Gauge

Typical setting: Settings vary greatly for each unit.
(see Reference section for adjusting information)

Check the Supply Gas Pressure

Check the supply gas pressure and compare it with
the unit’s nameplate pressure requirements. Adjust
the supply regulator as needed until the supply gas
pressure is within the specified range. The direct gas
nameplate is located on the outside of the unit on the
control center side.

Check the Pilot Gas Pressure

Check the pilot gas pressure. The recommended
gas pressure is 3 in. wg. Adjust the pilot regulator as
needed. See the Gas Train Layout in the Reference
section for the location of the pilot pressure test port
and pilot regulator.

Check the Optional High and Low Gas Pressure
Switches

Check the settings on the high and low gas pressure
switches. The high gas setting is typically 8 in. wg
(2 kPa) and the low gas setting is typically 3 in. wg
(0.7 kPa). The switches are set at the factory and should
not need adjustment. Adjust the settings if needed. See
the Gas Train Layout in the Reference section for the
high and low pressure switch location.

Start-Up - Direct Gas

IMPORTANT

For proper unit function and safety, follow the start-up
procedure in the exact order that it is presented.

IMPORTANT

This start-up should begin after all of the installation
procedures and the blower start-up have been
completed.

Direct Gas Nameplate

“ WC

“ WC

“ WC

F

PSI

“ WC

“ WC

MAX BTU/HR

BTU/H MAX

NORMAL MANIFOLD

PRESSURE

PRESSION DÕADMISSION

NORMALE

MIN GAS

PRESSURE

PRESSION DE GAZ

MIN BURNER

PRESSURE DROP

PERTE MIN DE PRESSION

DANS LE BRULEUR

TYPE OF GAS

NATURE DU GAZ

MIN BTU/HR

BTU/H MIN

MIN GAS PRESSURE

FOR MAX OUTPUT

PRESSION DE GAZ MIN

POUR PUISSANCE MAX

MAX BURNER

PRESSURE DROP

PERTE MAX DE PRESSION

DANS LE BRULEUR

MAX GAS

PRESSURE

PRESSION DE GAZ

MAX

DESIGN ΔT

ΔT NORMALE

EQUIPPED FOR

CONCU POUR

SCFM

“ WC

EXTERNAL STATIC PRESSURE

PRESSION STATIQUE EXTERIEURE

AGAINST

CONTE

Minimum and maximum gas

pressures for maximum output

Type of gas

IMPORTANT

The purpose of the high and low gas pressure
switches is to automatically shut down the burner
if the inlet gas pressure is too low for the burner to
safely light, or if the manifold pressure is too high for
the burner to operate properly.