Maintenance - routine, V-belt drives, Motors – Greenheck Fan VSU Make-Up Air Unit with Direct-Fired Gas Heater 470654 User Manual

Page 31: Wheels, Filters

Advertising
background image

31

Model VSU Make-Up Air

®

Maintenance - Routine

CAUTION

Lock-out the gas and the electrical power to the
unit before performing any maintenance or service
operations to this unit.

V-Belt Drives

V-belt drives must be checked on a regular basis for
wear, tension, alignment, and dirt accumulation.

Check the tension by measuring the deflection in the
belt as shown below.

Check the alignment by using a straight edge across
both sheaves as shown below.

Motors

Motor maintenance is generally limited to cleaning and
lubrication (where applicable).

Cleaning should be limited to exterior surfaces only.
Removing dust and grease build-up on the motor
assures proper motor cooling.

Motors supplied with grease fittings should be
greased in accordance with the manufacturer’s
recommendations.

Wheels

Wheels require little attention when moving clean air.
Occasionally oil and dust may accumulate on the wheel
causing imbalance. When this occurs the wheel and
housing should be cleaned to assure proper operation.

Belt Tension

Belt Span

Deflection =

Belt Span

64

Drive Alignment

IMPORTANT

Premature or frequent belt failures can be caused by
improper belt tension or misaligned sheaves.

• Abnormally high belt tension or drive misalignment

will cause excessive bearing loads and may result in
failure of the fan and/or motor bearings.

• Abnormally low belt tension will cause squealing on

start-up, excessive belt flutter, slippage, and
overheated sheaves.

IMPORTANT

Do not pry belts on or off the sheave. Loosen belt
tension until belts can be removed by simply lifting the
belts off the sheaves.

IMPORTANT

When replacing V-belts on multiple groove drives,
all belts should be changed to provide uniform drive
loading.

IMPORTANT

Do not install new belts on worn sheaves. If the
sheaves have grooves worn in them, they must be
replaced before new belts are installed.

IMPORTANT

Do not allow water or solvents to enter the motor
or bearings. Motors and bearings should never be
sprayed with steam, water or solvents.

IMPORTANT

Greasing motors is only intended when fittings are
provided. Many motors are permanently lubricated,
requiring no additional lubrication.

Filters

Filter maintenance is generally limited to cleaning and
replacement.

Aluminum mesh filters can be washed in warm soapy
water.

An adhesive spray can be added to aluminum mesh
filters to increase their efficiency.

IMPORTANT

When reinstalling filters, be sure to install them with
the airflow in the correct direction. An airflow direction
arrow is located on the side of the filters.

IMPORTANT

Replacement filters should be from the same
manufacturer and the same size as the original filters
provided with the unit.