Troubleshooting, Motor overamps – Greenheck Fan VSU Make-Up Air Unit with Direct-Fired Gas Heater 470654 User Manual

Page 23

Advertising
background image

23

Model VSU Make-Up Air

®

Motor Overamps

Troubleshooting

Air volume too high?

Adjust drives or increase external

static pressure as needed.

Reference: Start-Up - Blower, Air Volume Measurement and Check, pg. 14

Motor horsepower too low?

Resize motor.

Motor voltage correct?

Provide proper power supply.

Reference: Start-Up - Blower, Check the Voltage, pg. 14

Blower rotation correct?

Reverse blower rotation.

Reference: Start-Up - Blower, Check the Blower Rotation

Actual static pressure

lower than design?

Adjust drives to reduce blower RPM.

Reference: Start-Up - Blower, Air Volume Measurement and Check, pg. 14

No

No

Yes

Yes

Yes

Yes

No

Yes

No

No

Shorted windings in motor?

Replace motor.

Yes

Everything is working

properly, consult factory.

Yes