4 description of control terminals, 5 protections, 1 internal protection components – GE CS300 User Manual

Page 12: 2 internal fuses, 4 description of control terminals 2.5 protections, 5 protections 2.5.1 internal protection components

Advertising
background image

GEH-6639

——————— INSTRUCTION MANUAL ————————

12

2.4 DESCRIPTION OF CONTROL TERMINALS

Terminals

Function

Voltage, Current

23

Input of the precharge enable control

(15 - 35V, 5 - 11mA)

32

Output of the MLP static signal (low - active signal)

(5 … 35V, 20mA source)

33

(Common) Ground of the MLP and ML static signals

-

34

Reference point for Power supply +24V

-

35

Power supply output +24V

(32V / 300mA max)

36

Output of the ML signal (low - active signal)

(5 … 35V, 20mA max sink)

37

Power supply of the ML and MLP signals

(35V max)

52

(Common) Ground of the precharge enable control

-

70, 72

OK Relay

(max 250V, 1A – AC11)

cs020

2.5 PROTECTIONS

2.5.1 Internal Protection Components

Converter

Designation

Varistors

6KCS3185-480
6KCS3280-480
6KCS3420-480

575 V / 220 J

6KCS3650-480

Ø 20 mm

6KCS310H-480
6KCS315H-480

cs025

V1, V2, V3

2.5.2 Internal Fuses

Converter

Designation

Fuses

Designation

Fuses for

Fuses

6KCS3185-480
6KCS3280-480

16 A / 500 V

6KCS3420-480

fast 6 x 32 mm

6KCS3650-480

6KCS310H-480

25 A / 500 V

6KCS315H-480

fast 6 x 32 mm

cs030

F1, F2, F3

F4

Power supply protection 4 A, 250 V fast 6,3 x 32

F5

+24V protection

1 A, 250 V slow 5 x 20

Advertising