Installation – Greenheck Fan Vektor-ERS Energy Recovery Plenum Laboratory Exhaust 474118 User Manual

Page 4

Advertising
background image

4

Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust

CAUTION

When installing an ERS plenum cabinet, ensure
the proper protective devices are used to protect
personnel from moving parts and other hazards.

Check local codes to ensure compliance for all
protective devices.
ERS plenum cabinet with coil section should be lifted/
hoisted by lifting brackets provided. These brackets
are located around the lower perimeter of the plenum
cabinet.
1. Before lifting, be sure that all shipping material

has been removed from unit.

2. To assist in determining rigging requirements,

weights are shown below.

3. Unit must be lifted by the lifting brackets

provided on base structure.

4. Rigger to use suitable mating hardware to attach

to unit lifting brackets.

5. Two spreader bars must span the unit to prevent

damage to the cabinet by the lift cables.

6. Always test-lift the unit to check for proper

balance and rigging before hoisting to desired
location.

7. Never lift units in windy conditions.
8. Preparation of curb and roof openings should be

completed prior to lifting unit to the roof. Verify
the curb has the gasket seal on the top surface.

9. Do not use fork lifts for handling unit.

Cabinet

Size

Cabinet

Height

Weight

(lbs)*

020

075

3700

090

4500

030

075

4300

090

4900

040

075

5400

090

6100

060

075

6900

090

7800

110

8300

* Weights shown are for largest coil and filter

options per cabinet size. Based on dry
weight. Weights for custom designed units
may vary.

Unit Weights (ERS Plenum Section Only)

Installation

ERS plenum cabinets and fan bypass air plenums
are to be rigged and moved by the lifting brackets
provided. Handle
in such a manner
as to keep from
scratching or
chipping the
coating. Damaged
finish may reduce
ability of cabinet
to resist corrosion.
See coating repair
section of this
manual for details
involving touch-
up of damaged
surfaces.

Service

Door

Service

Door

Service

Door

TOP VIEW

of

PLENUM SECTION

Lifting Bracket

(removable after

installation)

ERS Plenum Housing

Roof Curb

Fan Bypass

Air Plenum

Lift Points

Top view of

Bypass Air Plenum

Advertising