Duct connections – Greenheck Fan Vektor-ERS Energy Recovery Plenum Laboratory Exhaust 474118 User Manual

Page 7

Advertising
background image

7

Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust

Duct Connections

Plenum Bottom Inlet Opening

Plenum Side Inlet Duct Dimension

Cabinet

Size

Length

(inches)

Width

(inches)

020

86

25

030

120

25

040

172

25

060

236

25

Cabinet

Size

Length

(inches)

Height

(inches)

020

86

30

030

120

30

040

172

30

060

236

30

Length

Gasket or Sealant

(by others)

Gasket or Sealant

(by others)

Screws

(by others)

Contractor

Installed

Ductwork

Height

Length

Width

Service

Door

Service

Door

Service

Door

Bottom Inlet

Plenum Side Inlet

Length

Gasket or Sealant

(by others)

Gasket or Sealant

(by others)

Screws

(by others)

Contractor

Installed

Ductwork

Height

Energy Recovery Cabinet

Energy Recovery Cabinet

Roof Deck

Curb

Curb

Roof Deck

RECOMMENDED DUCT INSTALLATION FOR VEKTOR ENERGY RECOVERY VERTICAL INLETS

NOTE:

-ALL DUCT WORK AND HARDWARE SUPPLIED BY OTHERS

-CAULK AND/OR GASKETING MATERIAL SHOULD BE USED TO SEAL DUCT TO VEKTOR ERS CABINET

Contractor

Installed

Ductwork

Contr actor

Installed

Ductwork

Energy Recovery Cabinet

Energy Recovery Cabinet

Roof Deck

Curb

Curb

Roof Deck

RECOMMENDED DUCT INSTALLATION FOR VEKTOR ENERGY RECOVERY VERTICAL INLETS

NOTE:

-ALL DUCT WORK AND HARDWARE SUPPLIED BY OTHERS

-CAULK AND/OR GASKETING MATERIAL SHOULD BE USED TO SEAL DUCT TO VEKTOR ERS CABINET

Contractor

Installed

Ductwork

Contr actor

Installed

Ductwork

Duct Connections

Installation of all ducts should be done in accordance
with SMACNA and AMCA guidelines.
Connect primary exhaust air ducts to unit using
flanged connections. Screw ducts directly to unit
using stainless steel self-tapping sheet metal screws.
Contractor is responsible for providing transitions
to accommodate difference in sizing between unit
and building ducts. Duct connections to collar-type
openings can be made with S-cleats or overlapping
joints. Apply caulking around the duct connection.
Failure to ensure a tight fit and properly seal duct
connections can cause air leakage and system
performance problems from the contaminated
airstream.