Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust

Plenum Service Clearances and

Access Locations

ERS plenum cabinet and Vektor fan bypass air plenum
(BAP) require minimum clearances for access on three
sides for routine maintenance. Filter replacement,
drain pan inspection and cleaning, coil inspection,
damper actuator adjustments and inspection, fan
bearing lubrication and belt adjustment (belt drive
units), are examples of routine maintenance that must
be performed. Coil and filter sections are always
provided with a service door or panel for proper
component access. Clearances for component
removal may be greater than the service clearances.
Refer to page 12 for coil clearances.

2 . Cut roof opening and locate curb

Layout the unit roof openings such that exhaust

inlet of the unit will line up with the corresponding
ductwork (refer to Recommended Roof Openings
on page 7). Do not make opening larger than
necessary. Be sure to allow for the recommended
service clearances.

3 . Install roof curbs

Locate curb over roof opening. Check that the

diagonal dimensions are within ±1⁄8 inch of each
other and adjust as necessary. Shim as required
to level. Secure curb to roof deck. Attach
supplied gasketing to top of curb.

4 . Set the ERS plenum cabinet

Lift ERS plenum cabinet to a point directly above

the curb and duct openings. While lowering,
guide cabinet to align with duct opening. Roof
curbs fit inside the unit base. Set ERS plenum
cabinet into place on assembled VK-ERS roof
curb. Allow gasketing on curb to compress before
setting the fan bypass air plenum. Make sure the
unit is properly seated on the curb and is level.

8 ROW COIL

193.8"

EXTERNAL

PIPING BY OTHERS

SERVICE DOOR

155"

INTAKE OPENING

NEMA 3R DISCONNECT

INSPECTION PANEL

1" DRAIN

(PER FAN)

VK-MD-33 (QTY. 2)

ROOF CURB

1.5" DRAIN

BOTH SIDES

.75" DRAIN

LIFT LUG

(QTY. 8)

S

S

S

S

S

S

38"

126.5"

ISOLATION DAMPER

SIDE INLET

Coil

Coil

Optional
External
Piping

(by others)

Service Doors

Internal Pipe
Chase

Side or Bottom Intake Opening

Lift
Bracket

Optional
Internal
Piping

(by others)

under

Vektor fans

Bypass
Weatherhood(s)

Vektor bypass
air plenum
optional mounting
locations shown

Filters

Coil

Single and Dual Coil Removal Clearances

Coil

Coil

Service Doors

Coil Service

Clearance

Coil Service

Clearance

WEIGHTS (LBS)

CURB

600

FAN (QTY. 2)

4580

FAN BAP

2750

ERS PLENUM

3700

TOTAL

11630

Clearance

Clearance

Used on page 5 of Part #474118 - need to copy, and edit this same drawing for use on backcover of same Instruction.

Used on backcover of Part #474118

NOTE

Gasketing material (shipped with Vektor fan) should
be placed on the top edge of secured roof curb
prior to placing the ERS plenum cabinet and Vektor
bypass air plenum on the curb.

NOTE

If fan bypass air plenum (BAP) is in sections, these
should be assembled first, prior to connection to
ERS plenum cabinet. Refer to Vektor Fan IOM (part
number 464652) on how to assemble the fan BAP.

Determine the placement of the plenum sections
relative to each other. Please refer to the submittal
drawing for the orientation of any bypass air plenum
(BAP) dampers or air inlet locations.

Roof Curb

ERS

Plenum

Cabinet

Pre-installed
gasket material

ERS Plenum Cabinet

Installed on Roof Curb

Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be clear
of structural members of the building.
1 . Assemble factory supplied roof curbs

Roof curbs are Model VK-ERS, which are shipped

knocked down and require field assembly (by
others). Assembly instructions are included with
the roof curb.

Anchor curb to roof deck structure in accordance

with project construction documents.

Curb section

for ERS plenum

cabinet

Curb section

for Vektor fan

bypass air

plenum

Gasketing material

(supplied) to be

attached to top edge

of all curb sections

Assembly of Roof Curbs and ERS Plenum

Cabinet to the Bypass Air Plenum (BAP)

Advertising