Filter replacement, Coil installation checklist, External pipe connection external pipe connection – Greenheck Fan Vektor-ERS Energy Recovery Plenum Laboratory Exhaust 474118 User Manual

Page 9

Advertising
background image

9

Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust

Coil Installation Checklist

Use the following checklist to verify that all necessary
installation procedures have been completed.
1. Coils are installed with airflow in same direction

as indicated on the coil nameplate or casing.

2. Condensate drain pans and piping is installed

with a trap in the condensate line and piping is
insulated and heated if installed in applications
that are below freezing.

3. Clean filters are installed upstream.

6. Pipe sizes for the system must be selected on the

basis of the head [pressure] available from the
circulating pump.

7. Internal coil plumbing. Under each fan there is

a raised, insulated cover panel to be used when
internal pipe connections are desired. Either
remove this panel to run plumbing or punch
appropriately sized holes in the panel to allow
piping to pass without rubbing and space for
piping insulation, sealant and grommets (by
others).

NOTE

Vent and drain connections are provided on
Greenheck water coils unless otherwise specified.
This allows the coils to be drained. Keep in mind
that when draining the coils, all water may not drain
from the coil. In order to completely drain the coil
to prevent the possibility of freezing during cold
ambient temperatures, air or nitrogen pressure must
be utilized to blow any remaining water from the
coil.

Filter Replacement

Filters are located only in the coil plenum section.
Access is needed from both sides of the plenum to
change all the filters. Unit may have either 2 inch
MERV 8 filters or 4 inch MERV 11 filters depending on
the application requirements. Use equivalent MERV
rating filters when replacing.
Change the filters regularly. Pressure drop readings
can be used to determine when a filter should be
replaced. Prefilters should be replaced at filter
manufacturers recommended pressure drop change
out or as required by system design.
All filter sections have access provided by a door.
Filters used in Greenheck ERS plenums can be
changed in most cases by sliding them out and
replacing. In some cases, filters are secured to frames
using a clip.

SUPPLY

RETURN

TEXT COLOR: BLUE

LABEL COLOR: WHITE

NOTE:

Airflow

SUPPLY

CAP

RETURN

CAP

Airflow

QTY

DESCRIPTION

MAT'L

PART NO.

PAINT

462708

VINYL

CW4R,6R,8R COIL RIGHT OUTLET

1

OLUND_T

11/20/2002

1/1

IAN7664

MSCF-15,20,25

30,45,50,65,85

P/N 462708

The original drawing. Dan Jore asked me to edit 8/10/2010.
Remove the border and the two cap drawings.

PURCHASED

COILCONNECTION

LABELCW-RIGHT

P/N 462682

RETURN

SUPPLY

LABEL COLOR: WHITE
TEXT COLOR: BLUE

NOTE:

Airflow

RETURN

SUPPLY

CAP

CAP

Airflow

QTY

DESCRIPTION

MAT'L

PART NO.

PAINT

462682

VINYL

CW4R,6R,8R COIL LEFT OUTLET

1

OLUND_T

11/20/2002

1/1

IAN7664

MSCF-15,20,25

30,45,50,65,85

The original drawing. Dan Jore asked me to edit 8/10/2010.
Remove the border and the two cap drawings.

PURCHASED

COILCONNECTION

LABELSCW-LEFT

Internal

Pipe

Chase

Internal

Pipe

Chase

External Pipe

Connection

External Pipe

Connection