OM-818 Page 16

3-9.

Connecting Input Power To Rack

Have only qualified persons make
this installation.

Y

Turn Off welding power
sources before inspecting
or installing rack.

1

Control Box

Open access door.

2

Line Disconnect Device Of
Proper Rating

3

Input Conductors

4

Grounding Conductor

Select size and length using Sec-
tion 3-10 or 3-11. Conductors must
be able to carry the combined am-
perage draw of all welding power
sources mounted on the rack. Con-
ductor insulation must comply with
national, state, and local electrical
codes.

5

Strain Relief Connector

Insert conductors through strain
relief.

6

Input Terminal Block

7

Line Terminals

8

Ground Terminal

Connect grounding conductor to
ground terminal first. Then connect
input conductors to line terminals.

Close control box access door.

Install grounding conductor and in-
put conductors in conduit or equiv-
alent to deenergized line discon-
nect device.

Connect grounding conductor first,
then line input conductors.

Be sure grounding conductor goes
to an earth ground.

9

Overcurrent Protection

Select type and size using Section
3-10 or 3-11. Install into deen-
ergized line disconnect device
(fused disconnect switch shown).

ST-801 702 / Ref. ST-801 703

1

6

8

4

5

2

3

7

3

4

9