OM-818 Page 17

3-10. Electrical Service Guide For XMT 304 4-Racks

Input Voltage

230

460

575

Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes

200

110

90

Min Input Conductor Size In AWG/Kcmil

2

6

8

Max Recommended Input Conductor Length

In Feet (Meters)

210 (64)

301 (92)

300 (91)

Min Grounding Conductor Size In AWG/Kcmil

6

6

8

Reference: 1996 National Electrical Code (NEC).

S-0092J

3-11. Electrical Service Guide For XMT 304/EX 300 6-Racks

Input Voltage

230

460

575

Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes

300

175

125

Min Input Conductor Size In AWG/Kcmil

1/0

2

4

Max Recommended Input Conductor Length

In Feet (Meters)

215 (66)

451 (137)

467 (142)

Min Grounding Conductor Size In AWG/Kcmil

4

6

6

Reference: 1996 National Electrical Code (NEC).

S-0092J

3-12. Electrical Service Guide For XMT 456/Invision 456 Racks (Customer-Installed Only)

Input Voltage*

460

575

Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes

200

175

Min Input Conductor Size In AWG/Kcmil

2

2

Max Recommended Input Conductor Length

In Feet (Meters)

210 (64)

451 (137)

Min Grounding Conductor Size In AWG/Kcmil

6

8

* Due to current demands, a rack containing XMT/Invisions 456 requiring 230/460 volt input power must be connected to 460 volt input power
only.

Reference: 1996 National Electrical Code (NEC).