Page 14

Advertising
background image

OM-157 066 Page 10

2-11. Electrical Service Guide

Input Voltage

200

230

460

575

Input Amperes At Rated Output

46

40

20

16

Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes

Circuit Breaker

1

,

Time-Delay Fuse

2

50

50

25

20

Normal Operating Fuse

3

70

60

30

25

Min Input Conductor Size In AWG/Kcmil

10

10

14

14

Max Recommended Input Conductor Length In Feet (Meters)

59

(18)

77

(24)

122

(37)

190

(58)

Min Grounding Conductor Size In AWG/Kcmil

10

10

14

14

Reference: 1999 National Electrical Code (NEC)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

Y

Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.

2-12. Selecting A Location And Connecting Input Power

1

Rating Label

Supply correct input power.

2

Plug

3

Receptacle

Connect plug to receptacle.

4

Line Disconnect Device

See Section 2-11.

Y

Special installation may be
required where gasoline or
volatile liquids are present –
see NEC Article 511 or CEC
Section 20.

ST-800 923-A

L1

L2

230 VAC, 1

18 in (457 mm) of
space for airflow

L1

L2

1

Y

Do not move or operate unit
where it could tip.

Y

Always connect
grounding conductor first.

= GND/PE

3

2

4