Miller Electric Renegade 180 User Manual

Page 25

Advertising
background image

.

Complete Parts List available at www. MillerWelds.com

OM-228 042 Page 21

5-9. Connecting Single−Phase, 230 Volt AC Utility Input Power

.

This unit can provide weld out-
put using the engine to power

the welding power source/wire

feeder OR single−phase 230

volt ac utility power can be

used to power the welding pow-

er source/wire feeder.
Installation must meet all Na-

tional and Local Codes −

have only qualified persons

make this installation.
Disconnect and lockout/tag-

out input power before con-

necting input conductors

from unit.
Always connect green or

green/yellow conductor to

supply grounding terminal

first, and never to a line ter-

minal.

1

Rating Label

Supply correct input power.
2

Black And White Input

Conductor (L1 And L2)

3

Green Or Green/Yellow

Grounding Conductor

4

Input Power Cord.

5

Disconnect Device (switch

shown in the OFF position)

6

Disconnect Device Grounding

Terminal

7

Disconnect Device Line

Terminals

Connect green or green/yellow

grounding conductor to disconnect

device grounding terminal first.
Connect input conductors L1 and

L2 to disconnect device line termi-

nals.
8

Over-Current Protection

Select type and size of over-current

protection using Section 5-10

(fused disconnect switch shown).
Close and secure door on discon-

nect device. Remove lockout/tag-

out device, and place switch in the

On position.
9

Plug (NEMA 6-50P)

10 Receptacle (NEMA 6-50R)
Connect plug to receptacle.

Special installation may be

required where gasoline or

volatile liquids are present −

see NEC Article 511 or CEC

Section 20.

Ref. 802 085 / Ref. 803 766-B / 804 476-C

1

L1

L2

9

230 VAC, 1

10

Tools Needed:

5

4

L1

L2

1

=GND/PE Earth Ground

3

2

6

7

8

.

Shown with optional cylinder rack