0 installation – Maytag Ventilation Systems HRV-210 User Manual

Page 13

Advertising
background image

13

6.0

Installation

6.1 A

DJUSTING THE

D

AMPER

R

OD

(F

OR

ERV

S

I

NSTALLED IN

W

ARM

R

EGIONS

)

Refer to Section 4.2 and observe the difference in the damper
position at the right in diagrams Defrost Mode 1 and Defrost Mode 2:
for Defrost Mode 1 the damper is completely closed, whereas
for Defrost Mode 2 the damper is half closed. At the factory, all ERVs
are assembled for defrost Mode 2. Therefore, if your installation
is for an ERV in a warm region (zone D as defined in Section 3),
the rod must be moved to position 1 (see figure 5).

NOTE: Before attempting to change the position of the damper

rod, place the unit on a table for easy access and remove
the recovery core.

6.2 L

OCATING AND

M

OUNTING THE

U

NIT

Choose an appropriate location for the unit:

Within an area of the house where the temperature is above 10°C /
50°F (basement, attic, furnace room, laundry room, etc.).

Away from living areas (dining room, living room, bedroom), if possible.

So as to provide easy access to the interior cabinet and to
the control panel on the right hand side of the unit.

Close to an exterior wall, so as to limit the length of the insulated
flexible duct to and from the unit.

Close to a drain. If no drain is close by, use a pail to collect
run-off.

Away from hot chimneys, electrical panel and other fire haz-
ards.

Allow for a power source (110 V standard outlet).

Hang the unit to ceiling joists with the 4 chains and
springs provided (see figures 6 and 7).

VD0064

VD0038

figure 6

figure 7

CAUTION

Make sure the unit is level.

CAUTION

This is a delicate operation: to avoid injury proceed carefully and use the appropriate tools.

VO0015

O00 5

1

2

figure 5

I

NSPECT THE

C

ONTENTS OF THE

B

OX

Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door
latches, door hinges, dampers, duct collars, cabinet, etc.

Inspect the interior of the unit for damage. Ensure that the fan motor assembly, recovery core, insulation,
dampers, damper actuator and drain pan are all intact.

If the unit was damaged during shipping, contact your local distributor. (Claim must be made within
24 hours after delivery.)

Use checklist included with the unit to ensure that no parts are missing.

Advertising
This manual is related to the following products: