SECTION 7 − OPERATING AUXILIARY EQUIPMENT

Set Current control to maximum for full generator power output at AC receptacles.

NOTE

7-1. Generator Power Panel Receptacles

Y If unit does not have GFCI recep-

tacles, use GFCI-protected exten-

sion cord.

.

Generator power decreases as weld

current increases.

1

240 V AC Receptacle RC1

RC1 supplies 60 Hz single-phase power at

weld/power speed. Maximum output is 4.5

kVA/kW (peak) or 4 kVA/kW (continuous).

2

120 V 20 A AC Duplex Receptacle

RC2

3

120 V 20 A AC Duplex Receptacle

RC3

RC2 and RC3 supply 60 Hz single-phase

power at weld/power speed. Maximum

output from RC2 or RC3 is 2.4 kVA/kW.

.

Do not parallel the two 120V duplex
receptacles.

4

Supplementary Protector CB1

CB1 protects the receptacles from over-

load. If CB1 opens, the receptacles do not

work. Move switch to the On position to re-

set.

.

If supplementary protector continues
to open, contact Factory Authorized

Service Agent.

Combined output of all receptacles limited

to 4 kVA/kW continuous rating of the gen-

erator (See Section 11 − Generator Power

Guidelines).

EXAMPLE: If 10 A is drawn from each 120

volt duplex receptacle, only 6 A is available

from the 240 V receptacle.

2 x (120 V x 10 A) + (240 V x 6 A) = 4 kVA/

KW.

218 610−B