12. electrical service guide – Miller Electric 852 User Manual

Page 24

Advertising
background image

.

A complete Parts List is available at www.MillerWelds.com

OM-222 Page 20

4-12. Electrical Service Guide

60 Hertz Models

300 Amp Model

450 Amp Model

650 Amp Model

Input Voltage

200

230

460

575

200

230

460

575

230

460

575

Input Amperes At Rated Output

70

61

31

25

102

89

45

36

124

62

50

Max Recommended Standard Fuse

Rating In Amperes

1

Time-Delay

2

80

70

35

30

125

110

50

45

150

70

60

Normal Operating 3

110

90

45

35

150

125

70

50

175

90

70

Min Input Conductor Size In AWG

4

6

8

10

12

4

4

8

10

3

8

8

Max Recommended Input Conductor

Length In Feet (Meters)

149

(45)

131

(40)

356

(108)

342

(104)

136

(41)

180

(55)

319

(97)

335

(102)

144

(44)

210

(64)

328

(100)

Min Grounding Conductor Size In

AWG

4

6

8

10

12

6

6

8

10

6

8

8

Reference: 2005 National Electrical Code (NEC)

1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

50 Hertz Models

300 Amp Mode

l

450 Amp Model

650 Amp Model

Input Voltage

380

400

440

380

400

440

380

400

440

Input Amperes At Rated Output

35

33

31

54

51

47

75

71

65

Max Recommended Standard Fuse Rating In

Amperes

1

Time-Delay

2

40

40

35

60

60

50

90

80

80

Normal Operating 3

60

50

50

80

80

70

125

110

100

Min Input Conductor Size In AWG

4

10

10

10

8

8

8

6

6

6

Max Recommended Input Conductor Length

In Feet (Meters)

243

(74)

269

(82)

326

(99)

218

(66)

241

(73)

292

(89)

219

(67)

242

(74)

293

(89)

Min Grounding Conductor Size In AWG

4

10

10

10

8

8

8

6

6

8

Reference: 2005 National Electrical Code (NEC)

1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.